Industrial Automation Parts. Prompt replies from real people.

ABB OT160G3-3DS Isolating switch

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/24/2026

Q1Can you supply the ABB OT160G3-3DS?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the ABB OT160G3-3DS cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
OT160G3-3DS
Material Number
1SCA162532R1001
Manufacturer
ABB
Product ID
90210

Get a Free Quote

Request pricing and availability for OT160G3-3DS.

More parts to source? Send your whole list in one enquiry

Key specifications

Degree of Protection
Front IP20
Product Net Weight
0.412 kg
Rated Conditional Short-Circuit Current (Inc)
(160 A fuse, 400 V) 5 kA (125 A fuse, 415 V) 50 kA (80 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
acc. to IEC 60947-1 800 V
Rated Operational Power AC-23A (Pe)
(415 V) 55 kW (690 V) 55 kW
See all specifications

Product Highlights

  1. Current Ratings: Conventional free-air thermal current (Ith) and conventional thermal current (Ithe) are both 160 A, with AC-21A rating of 160 A at 415 V, 125 A at 690 V, and 80 A at 800 V
  2. Switching Capacity: AC-23A rated operational current of 125 A at 415 V and 63 A at 690 V, with rated operational power of 55 kW at both 415 V and 690 V
  3. Short-Circuit Withstand: Rated conditional short-circuit current of 50 kA with a 125 A fuse at 415 V or an 80 A fuse at 690 V, and 5 kA with a 160 A fuse at 400 V
  4. Terminations and Mounting: Screw terminals accept Cu conductors from 2.5 to 70 mm² (solid, stranded, or flexible) with 16-18 mm stripping length and 6 N·m tightening torque, door mounting, 3-pole, front-operated, line terminals reversible top or bottom
  5. Durability and Protection: Mechanical durability of 100,000 operations, front IP20 degree of protection, pollution degree 3, rated impulse withstand voltage 8 kV, and rated insulation voltage 800 V per IEC 60947-1
  6. Compliance and Auxiliaries: Complies with IEC 60947-3, supports up to 4 NO and 4 NC mounted auxiliary contacts, and handle is not included
OT160G3-3DS

Product Information

Technical Specifications

Specifications for OT160G3-3DS

ParameterValue
Degree of ProtectionFront IP20
Environmental Information1SCC301334D0201
Pollution Degree3
Product Net Width70 mm
Product Net Height102.5 mm
Product Net Depth / Length70 mm
Product Net Weight0.412 kg
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x Cu 2.5…4 mm² Solid 1/2x Cu 2.5…6 mm² Flexible 1x Cu 2.5…70 mm² Flexible 2x Cu 2.5…25 mm² Stranded 1x Cu 2.5…70 mm² Stranded 2x Cu 2.5…25 mm²
Conventional Free-air Thermal Current (Ith)160 A
Conventional Thermal Current (Ithe)160 A
Degree of ProtectionFront IP20
Handle TypeHandle not included
Maximum Mounted Auxiliary Contacts4 NO, 4 NC
Mechanical DurabilityNr. Operations 100000
Mounting TypeDoor mounting
Number of Poles3P
Operating ModeFront operated
Pollution Degree3
Position of Line TerminalsTop In - Bottom Out Bottom In - Top Out
Power Lossat Rated Operating Conditions per Pole 7.3 W
Rated Conditional Short-Circuit Current (Inc)(160 A fuse, 400 V) 5 kA (125 A fuse, 415 V) 50 kA (80 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Insulation Voltage (Ui)acc. to IEC 60947-1 800 V
ParameterValue
Rated Operational Current AC-21A (Ie)(415 V) 160 A (690 V) 125 A (800 V AC) 80 A
Rated Operational Current AC-22A (Ie)(415 V) 160 A (690 V) 125 A (800 V) 63 A
Rated Operational Current AC-23A (Ie)(415 V) 125 A (690 V) 63 A
Rated Operational Power AC-23A (Pe)(415 V) 55 kW (690 V) 55 kW
Rated Operational VoltageMain Circuit 800 V
Rated Short-Circuit Making Capacity (Icm)(690 V) 4.8 kA
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 2.5 kA for 0.2 s 3.3 kA
Recommended Screw DriverMain Circuit Hexagon 4
Special FunctionsNo
StandardsIEC60947-3
Switches Operating MechanismMechanism on Top of the Switch
Terminal TypeScrew Terminals
Tightening Torqueacc. IEC 60947-1 6 N·m
Wire Stripping LengthMain Circuit 16-18 mm Main Circuit 0.63-0.71 in
Wire Stripping LengthMain Circuit 16-18 mm Main Circuit 0.63-0.71 in
Recommended Screw DriverMain Circuit Hexagon 4
Tightening Torqueacc. IEC 60947-1 6 N·m
Tightening Torque UL/CSAUL 53 lbf·in
Object Classification CodeQ
ETIM 8EC000216 - Switch disconnector
ETIM 9EC000216 - Switch disconnector (low voltage)
UNSPSC39122233
IDEA Granular Category Code (IGCC)5290 >> Disconnect switch
eClassV11.1 : 27371403
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID1SCA162532R1001

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.