Product Model
OT630E22
Material Number
1SCA022777R8580
Manufacturer
ABB
Product ID
90146

Get a Free Quote

Request pricing and availability for OT630E22.

More parts to source? Send your whole list in one enquiry

Key specifications

Degree of Protection
Front IP00
Product Net Weight
7.6 kg
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 630 A (500 V) 630 A (690 V) 630 A (1000 V) 630 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 200 kW (400 ... 415 V) 355 kW (500 V) 400 kW (690 V) 630 kW
See all specifications

Product Highlights

  1. Pole Configuration: 4-pole isolating switch with the fourth pole on the right side, switched simultaneously with the main poles
  2. Current Ratings: Conventional free-air thermal current 630 A at 40 °C and fully enclosed thermal current 630 A, with AC-21A, AC-22A and AC-23A operational current of 630 A at 380 to 415 V, 500 V and 690 V
  3. Voltage and Short-Circuit Ratings: Rated operational voltage 1000 V, rated insulation voltage 1000 V, rated impulse withstand voltage 12 kV, short-circuit making capacity 80 kA at 690 V and short-time withstand current 20 kA for 1 s
  4. Operational Power: Rated operational power AC-23A of 200 kW at 220 to 240 V, 355 kW at 400 to 415 V, 400 kW at 500 V and 630 kW at 690 V
  5. Mounting and Terminals: Base mounting, front-operated mechanism between the poles, lug terminals with tightening torque 50 to 75 N·m, line terminals configurable as top in - bottom out or bottom in - top out
  6. Dimensions and Durability: 331 mm wide, 250 mm high and 140 mm deep, 7.6 kg net weight, mechanical durability 10000 operating cycles, front degree of protection IP00 and pollution degree 3
  7. Standards and Power Loss: Complies with IEC 60947-3 and has a power loss of 25 W per pole at rated operating conditions
OT630E22

Product Information

Technical Specifications

Specifications for OT630E22

ParameterValue
Degree of ProtectionFront IP00
Environmental Information1SCC301232D0201
Pollution Degree3
Product Net Width331 mm
Product Net Height250 mm
Product Net Depth / Length140 mm
Product Net Weight7.6 kg
Conventional Free-air Thermal Current (Ith)Θ = 40 °C 630 A
Conventional Thermal Current (Ithe)Fully Enclosed 630 A
Degree of ProtectionFront IP00
Distance Between PhasesStandard
Fourth Pole PositionRight Side
Fourth Pole TypeSwitched - Simultaneous Function
Handle TypeHandle and shaft not included
Lock TypeNo
Mechanical Durability10000
Mounting TypeBase mounting
Number of Poles4P
Operating ModeFront operated
Pollution Degree3
Position of Line TerminalsTop In - Bottom Out Bottom In - Top Out
Power Lossat Rated Operating Conditions per Pole 25 W
Rated Impulse Withstand Voltage (Uimp)12 kV
ParameterValue
Rated Insulation Voltage (Ui)acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)(380 ... 415 V) 630 A (500 V) 630 A (690 V) 630 A (1000 V) 630 A
Rated Operational Current AC-22A (Ie)(380 ... 415 V) 630 A (500 V) 630 A (690 V) 630 A
Rated Operational Current AC-23A (Ie)(380 ... 415 V) 630 A (500 V) 630 A (690 V) 630 A
Rated Operational Power AC-23A (Pe)(220 ... 240 V) 200 kW (400 ... 415 V) 355 kW (500 V) 400 kW (690 V) 630 kW
Rated Operational VoltageMain Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)(690 V) 80 kA
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 20 kA
Special FunctionsNo
StandardsIEC 60947-3
Switches Operating MechanismMechanism Between the Poles 22 (Between the Poles)
Terminal TypeLug terminals
Tightening Torqueacc. IEC 60947-1 50 … 75 N·m
Tightening Torqueacc. IEC 60947-1 50 … 75 N·m
Object Classification CodeQ
ETIM 8EC000216 - Switch disconnector
ETIM 9EC000216 - Switch disconnector (low voltage)
eClassV11.1 : 27371403
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID1SCA022777R8580