| Product Net Width | 140 mm |
|---|
| Product Net Depth / Length | 180.5 mm |
|---|
| Product Net Height | 227 mm |
|---|
| Product Net Weight | 5.4 kg |
|---|
| Number of Main Contacts NO | 3 |
|---|
| Number of Main Contacts NC | 0 |
|---|
| Number of Auxiliary Contacts NO | 1 |
|---|
| Number of Auxiliary Contacts NC | 1 |
|---|
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives. |
|---|
| Rated Operational Voltage | Main Circuit 690 V |
|---|
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Π= 40 °C 500 A |
|---|
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 500 A (690 V) 55 °C 400 A (690 V) 70 °C 325 A |
|---|
| Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 300 A (440 V) 55 °C 280 A (500 V) 55 °C 280 A (690 V) 55 °C 280 A (380400 V) 55 °C 305 A (220230240 V) 55 °C 305 |
|---|
| Rated Operational Power AC-3 (Pe) | (415 V) 160 kW (440 V) 160 kW (500 V) 200 kW (690 V) 250 kW (380400 V) 160 kW (220230240 V) 90 kW |
|---|
| Rated Breaking Capacity AC-3 | 8 x Ie AC-3 |
|---|
| Rated Making Capacity AC-3 | 10 x Ie AC-3 |
|---|
| Short-Circuit Protective Devices | gG Type Fuses 500 A |
|---|
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 2400 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 500 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 1100 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 3500 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1500 A |
|---|
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2500 A |
|---|
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour (AC-2 / AC-4) 150 cycles per hour (AC-3) 300 cycles per hour |
|---|
| Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 450 A (220 V) 3 Poles in Series, 40 °C 450 A |
|---|
| Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 450 A (220 V) 3 Poles in Series, 40 °C 450 A |
|---|
| Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 450 A (220 V) 3 Poles in Series, 40 °C 450 A |
|---|
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 600 V |
|---|