Product Model
AF305-30-00-12
Material Number
1SFL587002R1200
Manufacturer
ABB
Product ID
83334

Get a Free Quote

Request pricing and availability for AF305-30-00-12.

More parts to source? Send your whole list in one enquiry

Key specifications

Product Net Weight
3.9 kg
Rated Operational Voltage
Main Circuit 1000 V
Rated Frequency (f)
Main Circuit 50 / 60 Hz
Rated Operational Current AC-1 (Ie)
(1000 V) 40 °C 375 A (1000 V) 55 °C 325 A (1000 V) 60 °C 325 A (1000 V) 70 °C 260 A (690 V) 40 °C 500 A (690 V) 55 °C 400 A (690 V) 70 °C 325 A
Rated Operational Power AC-3 (Pe)
(415 V) 160 kW (440 V) 160 kW (500 V) 200 kW (690 V) 250 kW (1000 V) 185 kW (380 / 400 V) 160 kW (220 / 230 / 240 V) 90 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 2440 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 500 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 996 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 3050 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1409 A
See all specifications

Product Highlights

  1. Wide Control Voltage Range: 48 to 130 V AC at 50/60 Hz and 48 to 130 V DC, with coil operating limits of 0.85 x Uc minimum to 1.1 x Uc maximum at up to 70 °C
  2. Main Contacts: 3 normally open main contacts, no normally closed main contacts and no auxiliary contacts
  3. High Current and Power Ratings: AC-3 rating of 305 A at 380 to 440 V and 55 °C, AC-3 rated power up to 250 kW at 690 V, and AC-1 rating of 500 A at 690 V and 40 °C
  4. Short-Circuit and Switching Capability: AC-3 making capacity 10 x Ie, AC-3 breaking capacity 8 x Ie, and short-circuit protection with 500 A gG fuses
  5. Mechanical Durability: 5 million operating cycles with a maximum mechanical switching frequency of 300 cycles per hour
  6. Coil Consumption: Holding 17 V·A at 50/60 Hz or 2.5 W DC, pull-in 340 V·A at 50/60 Hz or 360 W DC
  7. Operate Time: 25 to 55 ms between coil energization and NO contact closing, 37 to 47 ms between coil de-energization and NO contact opening
  8. Main Circuit Connections: Bars for main terminals, flexible 2 x 70 to 185 mm², rigid aluminum cable 1 x 185 to 240 mm², and rigid copper cable 2 x 70 to 185 mm²
  9. Terminal Protection: Coil terminals IP20 and main terminals IP00 according to IEC 60529, IEC 60947-1 and EN 60529
  10. Ambient Air Temperature: -40 to 70 °C without a thermal overload relay and -25 to 50 °C with a thermal overload relay at 0.85 to 1.1 Uc
  11. Operating Altitude: Up to 3000 m without derating
  12. Dimensions and Weight: 140 mm wide, 180 mm deep, 225 mm high, 3.9 kg
AF305-30-00-12

Product Information

Technical Specifications

Specifications for AF305-30-00-12

ParameterValue
Product Net Width140 mm
Product Net Depth / Length180 mm
Product Net Height225 mm
Product Net Weight3.9 kg
Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO0
Number of Auxiliary Contacts NC0
Rated Operational VoltageMain Circuit 1000 V
Rated Frequency (f)Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 500 A
Rated Operational Current AC-1 (Ie)(1000 V) 40 °C 375 A (1000 V) 55 °C 325 A (1000 V) 60 °C 325 A (1000 V) 70 °C 260 A (690 V) 40 °C 500 A (690 V) 55 °C 400 A (690 V) 70 °C 325 A
Rated Operational Current AC-3 (Ie)(415 V) 55 °C 305 A (440 V) 55 °C 305 A (500 V) 55 °C 290 A (690 V) 55 °C 290 A (1000 V) 55 °C 131 A (380400 V) 55 °C 305 A (220230240 V) 55 °C 305 A
Rated Operational Power AC-3 (Pe)(415 V) 160 kW (440 V) 160 kW (500 V) 200 kW (690 V) 250 kW (1000 V) 185 kW (380400 V) 160 kW (220230240 V) 90 kW
Rated Breaking Capacity AC-38 x Ie AC-3
Rated Making Capacity AC-310 x Ie AC-3
Short-Circuit Protective DevicesgG Type Fuses 500 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 2440 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 500 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 996 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 3050 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1409 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 4600 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 3800 A
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour (AC-2 / AC-4) 150 cycles per hour (AC-3) 300 cycles per hour
Rated Operational Current DC-1 (Ie)(110 V) 1-Pole, 40 °C 500 A (220 V) 2 Poles in Series, 40 °C 500 A (220 V) 3 Poles in Series, 40 °C 500 A
Rated Operational Current DC-3 (Ie)(110 V) 2 Poles in Series, 40 °C 400 A (220 V) 3 Poles in Series, 40 °C 400 A
Rated Operational Current DC-5 (Ie)(110 V) 2 Poles in Series, 40 °C 400 A (220 V) 3 Poles in Series, 40 °C 400 A
ParameterValue
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)Main Circuit 8 kV
Mechanical Durability5 million
Maximum Mechanical Switching Frequency300 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)50 Hz 48 ... 130 V 60 Hz 48 ... 130 V DC Operation 48 ... 130 V
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 50 Hz 17 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 17 V·A Holding at Max. Rated Control Circuit Voltage DC 2.5 W Pull-in at Max. Rated Control Circuit Voltage 50 Hz 340 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 340 V·A Pull-in at Max. Rated Control Circuit Voltage DC 360 W
Operate TimeBetween Coil De-energization and NO Contact Opening 37 ... 47 ms Between Coil Energization and NO Contact Closing 25 ... 55 ms
Connecting Capacity Main CircuitFlexible 2 x 70 ... 185 mm² Rigid Al-Cable 1 x 185 ... 240 mm² Rigid Cu-Cable 2 x 70 ... 185 mm²
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² Flexible 1x0.75 ... 2.5 mm² Solid 2 x 1 ... 4 mm² Stranded 1 x 1 .... 4 mm²
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal TypeMain Circuit: Bars
Maximum Operating Voltage UL/CSAMain Circuit 1000 V
General Use Rating UL/CSA(600 V AC) 400 A
Horsepower Rating UL/CSA(200 V AC) Three Phase 100 hp (208 V AC) Three Phase 100 hp (220 ... 240 V AC) Three Phase 125 hp (440 ... 480 V AC) Three Phase 250 hp (550 ... 600 V AC) Three Phase 300 hp
Ambient Air TemperatureClose to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C Close to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude PermissibleWithout Derating 3000 m
Object Classification CodeQ
ETIM 7EC000066 - Power contactor, AC switching
ETIM 8EC000066 - Power contactor, AC switching
ETIM 9EC000066 - Power contactor, AC switching
eClassV11.0 : 27371003
UNSPSC39121529
IDEA Granular Category Code (IGCC)4758 >> Iec Contactors
E-Number (Finland)3706482
E-Number (Norway)3210158
Manufacturer ID1SFL587002R1200

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.