Q1Can you supply the ABB OT1600E03DDP?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the ABB OT1600E03DDP cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
OT1600E03DDP
Material Number
1SCA117174R1001
Manufacturer
ABB
Product ID
76280

Get a Free Quote

Request pricing and availability for OT1600E03DDP.

More parts to source? Send your whole list in one enquiry

Key specifications

Degree of Protection
Front IP00
Product Net Weight
47.5 kg
Rated Conditional Short-Circuit Current (Inc)
(1250 A fuse, 415 V) 80 kA (1250 A fuse, 500 V) 100 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Power AC-23A (Pe)
(400 ... 415 V) 710 kW (500 V) 900 kW (690 V) 1200 kW
See all specifications

Product Highlights

  1. Current Ratings: Conventional thermal current 1600 A fully enclosed, AC-21A and AC-22A rated operational current 1600 A at 380 to 690 V, AC-23A rated operational current 1250 A at 380 to 690 V
  2. Switching Capacity: Rated operational power AC-23A 710 kW at 400 to 415 V, 900 kW at 500 V, and 1200 kW at 690 V, with rated short-circuit making capacity 110 kA at 690 V and rated short-time withstand current 50 kA for 1 s
  3. Electrical Insulation and Protection: Rated insulation voltage 1000 V per IEC/EN 60664-1, rated impulse withstand voltage 12 kV, rated conditional short-circuit current 80 kA at 415 V and 100 kA at 500 V with a 1250 A fuse, pollution degree 3, front degree of protection IP00
  4. Configuration and Durability: Six poles, handle and shaft included, lockable, mechanical durability 6000 cycles, lug terminals with tightening torque 50 to 75 N·m per IEC 60947-1, power loss 48 W per pole at rated operating conditions
  5. Physical Data and Standard: Net dimensions 400 mm width, 372 mm height, 309 mm depth, net weight 47.5 kg, compliant with IEC 60947-3
OT1600E03DDP

Product Information

Technical Specifications

Specifications for OT1600E03DDP

ParameterValue
Degree of ProtectionFront IP00
Environmental Information1SCC301233D0201
Pollution Degree3
Product Net Width400 mm
Product Net Height372 mm
Product Net Depth / Length309 mm
Product Net Weight47.5 kg
Conventional Thermal Current (Ithe)Fully Enclosed 1600 A
Degree of ProtectionFront IP00
Handle ColorBlack
Handle TypeHandle and shaft included
Lock TypeYes
Mechanical Durability6000
Number of Poles6
Pollution Degree3
Power Lossat Rated Operating Conditions per Pole 48 W
Rated Conditional Short-Circuit Current (Inc)(1250 A fuse, 415 V) 80 kA (1250 A fuse, 500 V) 100 kA
Rated Impulse Withstand Voltage (Uimp)12 kV
Rated Insulation Voltage (Ui)acc. to IEC/EN 60664-1 1000 V
ParameterValue
Rated Operational Current AC-21A (Ie)(690 V) 1600 A (690 V) 380415V;1600 A (690 V) 500V;1600 A
Rated Operational Current AC-22A (Ie)(380 ... 415 V) 1600 A (500 V) 1600 A (690 V) 1600 A
Rated Operational Current AC-23A (Ie)(380 ... 415 V) 1250 A (500 V) 1250 A (690 V) 1250 A
Rated Operational Power AC-23A (Pe)(400 ... 415 V) 710 kW (500 V) 900 kW (690 V) 1200 kW
Rated Operational VoltageMain Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)(690 V) 110 kA
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 50 kA
StandardsIEC 60947-3
Terminal TypeLug terminals
Tightening Torqueacc. IEC 60947-1 50 … 75 N·m
Tightening Torqueacc. IEC 60947-1 50 … 75 N·m
Object Classification CodeQ
ETIM 8EC000229 - Handle for power circuit breaker
ETIM 9EC000229 - Handle for power circuit breaker
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID1SCA117174R1001