Product Model
OS400D04BBN2
Material Number
1SCA102291R1001
Manufacturer
ABB
Product ID
76063

Get a Free Quote

Request pricing and availability for OS400D04BBN2.

More parts to source? Send your whole list in one enquiry

Key specifications

Product Net Weight
9.1 kg
Number of Poles
4
Rated Conditional Short-Circuit Current (Inc)
(690 V) 80 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 132 kW (400 V) 220 kW (415 V) 230 kW (500 V) 280 kW (690 V) 400 kW
See all specifications

Product Highlights

  1. Rated Current: 400 A main circuit, with conventional free-air thermal current 400 A at 40 °C and fully enclosed thermal current 400 A
  2. Voltage and Short-Circuit Ratings: 690 V AC main circuit, 1000 V rated insulation voltage, 12 kV rated impulse withstand voltage, 80 kA rated conditional short-circuit current at 690 V, and 14 kA rms short-time withstand current for 1 s
  3. Configuration: 4-pole fuse switch disconnector with switched fourth pole on the right side, front-operated mechanism on the left side, and back-in back-out line terminals
  4. Fuse and Mounting: DIN fuse system accepting NH0, NH1, and NH2 fuse sizes, base mounting, lug terminals 25 mm wide, tightening torque 30 to 44 N·m
  5. Dimensions and Standards: 319 mm width, 230 mm height, 230 mm depth, 9.1 kg net weight, IEC 60947-3, pollution degree 3, 30 W power loss per pole at rated operating conditions
OS400D04BBN2

Product Information

Technical Specifications

Specifications for OS400D04BBN2

ParameterValue
Pollution Degree3
Product Net Width319 mm
Product Net Height230 mm
Product Net Depth / Length230 mm
Product Net Weight9.1 kg
Conventional Free-air Thermal Current (Ith)Θ = 40 °C 400 A
Conventional Thermal Current (Ithe)Fully Enclosed 400 A
Fourth Pole PositionRight Side
Fourth Pole TypeSwitched - With Solid Link
Fuse SizeNH0 NH1 NH2
Fuse SystemDIN
Handle TypeHandle and shaft not included
Mounting TypeBase mounting
Number of Poles4
Operating ModeFront Operated
Pollution Degree3
Position of Line TerminalsBack In - Back Out
Power Lossat Rated Operating Conditions per Pole 30 W
Rated Conditional Short-Circuit Current (Inc)(690 V) 80 kA
Rated Current (In)Main Circuit 400 A
Rated Impulse Withstand Voltage (Uimp)12 kV
Rated Insulation Voltage (Ui)1000 V
ParameterValue
Rated Operational Current AC-21A (Ie)(500 V) 400 A (690 V) 400 A
Rated Operational Current AC-22A (Ie)(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Current AC-23A (Ie)(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Power AC-23A (Pe)(220 ... 240 V) 132 kW (400 V) 220 kW (415 V) 230 kW (500 V) 280 kW (690 V) 400 kW
Rated Operational VoltageMain Circuit 690 V AC
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 14 kiloampere rms
StandardsIEC 60947-3
Switches Operating Mechanism04 (Left Side)
Terminal TypeLug terminals
Terminal Width25 mm
Tightening Torque30 ... 44 N·m
Tightening Torque30 ... 44 N·m
Object Classification CodeQ
ETIM 8EC001040 - Fuse switch disconnector
ETIM 9EC001040 - Fuse switch disconnector
UNSPSC39122233
IDEA Granular Category Code (IGCC)5291 >> Fuse switch disconnector
eClassV11.1 : 27371401
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID1SCA102291R1001

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.