| Rated Operational Current DC-3 (Ie) | (110 V) 1-Pole, 40 °C 8 A (110 V) 1-Pole, 60 °C 8 A (110 V) 1-Pole, 70 °C 8 A (110 V) 2 Poles in Series, 40 °C 30 A (110 V) 2 Poles in Series, 60 °C 30 A (110 V) 2 Poles in Series, 70 °C 26 A (110 V) 3 Poles in Series, 40 °C 30 A (110 V) 3 Poles in Series, 60 °C 30 A (110 V) 3 Poles in Series, 70 °C 26 A (220 V) 2 Poles in Series, 40 °C 8 A (220 V) 2 Poles in Series, 60 °C 8 A (220 V) 2 Poles in Series, 70 °C 8 A (220 V) 3 Poles in Series, 40 °C 30 A (220 V) 3 Poles in Series, 60 °C 30 A (220 V) 3 Poles in Series, 70 °C 26 A (72 V) 1-Pole, 40 °C 30 A (72 V) 1-Pole, 60 °C 30 A (72 V) 1-Pole, 70 °C 26 A (72 V) 2 Poles in Series, 40 °C 30 A (72 V) 2 Poles in Series, 60 °C 30 A (72 V) 2 Poles in Series, 70 °C 26 A (72 V) 3 Poles in Series, 40 °C 30 A (72 V) 3 Poles in Series, 60 °C 30 A (72 V) 3 Poles in Series, 70 °C 26 A |
|---|
| Rated Operational Current DC-5 (Ie) | (110 V) 1-Pole, 40 °C 4 A (110 V) 1-Pole, 60 °C 4 A (110 V) 1-Pole, 70 °C 4 A (110 V) 2 Poles in Series, 40 °C 20 A (110 V) 2 Poles in Series, 60 °C 20 A (110 V) 2 Poles in Series, 70 °C 20 A (110 V) 3 Poles in Series, 40 °C 30 A (110 V) 3 Poles in Series, 60 °C 30 A (110 V) 3 Poles in Series, 70 °C 26 A (220 V) 2 Poles in Series, 40 °C 4 A (220 V) 2 Poles in Series, 60 °C 4 A (220 V) 2 Poles in Series, 70 °C 4 A (220 V) 3 Poles in Series, 40 °C 16 A (220 V) 3 Poles in Series, 60 °C 16 A (220 V) 3 Poles in Series, 70 °C 16 A (72 V) 1-Pole, 40 °C 16 A (72 V) 1-Pole, 60 °C 16 A (72 V) 1-Pole, 70 °C 16 A (72 V) 2 Poles in Series, 40 °C 30 A (72 V) 2 Poles in Series, 60 °C 30 A (72 V) 2 Poles in Series, 70 °C 26 A (72 V) 3 Poles in Series, 40 °C 30 A (72 V) 3 Poles in Series, 60 °C 30 A (72 V) 3 Poles in Series, 70 °C 26 A |
|---|
| Rated Operational Current DC-13 (Ie) | (24 V) 6 A144 W (48 V) 2.8 A134 W (72 V) 1 A72 W (110 V) 0.55 A60 W (125 V) 0.55 A69 W (220 V) 0.27 A60 W (250 V) 0.27 A68 W (400 V) 0.15 A60 W (500 V) 0.13 A65 W (600 V) 0.1 A60 W |
|---|
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V acc. to IEC 60947-5-1 690 V acc. to UL/CSA 600 V |
|---|
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
|---|
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
|---|
| Rated Control Circuit Voltage (Uc) | 50 Hz 48 ... 130 V 60 Hz 48 ... 130 V DC Operation 48 ... 130 V |
|---|
| Operate Time | Between Coil De-energization and NC Contact Closing 13 ... 98 ms Between Coil De-energization and NO Contact Opening 11 ... 95 ms Between Coil Energization and NC Contact Opening 38 ... 90 ms Between Coil Energization and NO Contact Closing 40 ... 95 ms |
|---|
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
|---|
| Mounting by Screws (not supplied) | 2 x M4 screws placed diagonally |
|---|
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP10 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP10 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 |
|---|
| Terminal Type | Ring-Tongue Terminals |
|---|
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
|---|
| General Use Rating UL/CSA | (600 V AC) 30 A |
|---|
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 1-1/2 hp (200 ... 208 V AC) Three Phase 5 hp (220 ... 240 V AC) Three Phase 5 hp (240 V AC) Single Phase 3 hp (440 ... 480 V AC) Three Phase 10 hp (550 ... 600 V AC) Three Phase 15 hp |
|---|
| Tightening Torque UL/CSA | Auxiliary Circuit 11 in·lb Control Circuit 11 in·lb Main Circuit 13 in·lb |
|---|
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C Close to Contactor without Thermal O/L Relay -40 ... 70 °C Close to Contactor for Storage -60 ... +80 °C |
|---|
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
|---|
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
|---|
| Shock and Vibration Withstand acc. to IEC 61373 | Category 1, Class B |
|---|
| Object Classification Code | Q |
|---|
| ETIM 7 | EC000066 - Power contactor, AC switching |
|---|
| ETIM 8 | EC000066 - Power contactor, AC switching |
|---|
| ETIM 9 | EC000066 - Power contactor, AC switching |
|---|
| eClass | V11.0 : 27371003 |
|---|
| UNSPSC | 39121529 |
|---|
| IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
|---|
| Manufacturer ID | 1SBL176060R2210 |
|---|