| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V acc. to UL/CSA 600 V |
|---|
| Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 6 kV |
|---|
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
|---|
| Rated Control Circuit Voltage (Uc) | DC Operation 24 V |
|---|
| Operate Time | Between Coil De-energization and NC Contact Closing 15 ... 20 ms Between Coil De-energization and NO Contact Opening 13 ... 17 ms Between Coil Energization and NC Contact Opening 31 ... 53 ms Between Coil Energization and NO Contact Closing 36 ... 59 ms |
|---|
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1/2x 0.75 ... 1.5 mm² Rigid 1/2x 0.75 ... 2.5 mm² |
|---|
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1/2x 0.75 ... 1.5 mm² Rigid 1/2x 0.75 ... 2.5 mm² |
|---|
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1/2x 0.75 ... 1.5 mm² Rigid 1/2x 0.75 ... 2.5 mm² |
|---|
| Wire Stripping Length | Auxiliary Circuit 10 mm Control Circuit 10 mm Main Circuit 10 mm |
|---|
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 |
|---|
| Terminal Type | Spring Terminals |
|---|
| General Use Rating UL/CSA | (600 V AC) 15.2 A |
|---|
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 3/4 hp (200 ... 208 V AC) Three Phase 3 hp (220 ... 240 V AC) Three Phase 5 hp (240 V AC) Single Phase 2 hp (440 ... 480 V AC) Three Phase 10 hp (550 ... 600 V AC) Three Phase 10 hp |
|---|
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C Close to Contactor without Thermal O/L Relay -40 ... 70 °C Close to Contactor for Storage -60 ... +80 °C |
|---|
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
|---|
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
|---|
| Resistance to Shock acc. to IEC 60068-2-27 | Closed, Shock Direction: B1 10 g Closed, Shock Direction: C1 20 g Closed, Shock Direction: C2 20 g Open, Shock Direction: B1 5 g Open, Shock Direction: C1 9 g Open, Shock Direction: C2 14 g Shock Direction: A 20 g Shock Direction: B2 15 g |
|---|
| Resistance to Vibrations | 3g Closed Position & 2g Open Position 5 ... 300 Hz |
|---|
| Object Classification Code | Q |
|---|
| ETIM 7 | EC000066 - Power contactor, AC switching |
|---|
| ETIM 8 | EC000066 - Power contactor, AC switching |
|---|
| ETIM 9 | EC002552 - Power contactor, DC switching |
|---|
| eClass | V11.0 : 27371018 |
|---|
| UNSPSC | 39121529 |
|---|
| IDEA Granular Category Code (IGCC) | 4763 >> Power contactor, DC switching |
|---|
| Manufacturer ID | 1SBL123004R8132 |
|---|