Product Model
DDA802AC-63/0.3
Material Number
2CSB802001R3630
Manufacturer
ABB
Product ID
69615

Get a Free Quote

Request pricing and availability for DDA802AC-63/0.3.

More parts to source? Send your whole list in one enquiry

Key specifications

Rated Voltage (Ur)
230 V AC 240 V AC 400 V AC
Rated Operational Voltage
400/690 V
Rated Current (In)
63 A
Rated Frequency (f)
50/60 Hz
Degree of Protection
IP2X
Product Net Weight
300 g
See all specifications

Product Highlights

  1. Standards: IEC EN 60947-2 Ann. B
  2. Residual Current Type: Type AC, rated residual current 300 mA, maximum surge current 0.25 kA
  3. Electrical Ratings: rated current 63 A, rated voltage 230/240/400 V AC, rated operational voltage 400/690 V, rated insulation voltage 690 V, rated impulse withstand voltage 6 kV, rated frequency 50/60 Hz
  4. Compatible With: S800S, S800N, S800C, S800B
  5. Configuration: 2 poles, instantaneous operating characteristic, 4.5 modular spacings, 81 mm width, 108.2 mm height, 82.3 mm depth, 300 g net weight
  6. Connection and Environment: rigid 6 to 50 mm², flexible 6 to 70 mm², ambient temperature -25 to 60 °C, IP2X protection, 9 W power loss
DDA802AC-63/0.3

Product Information

Technical Specifications

Specifications for DDA802AC-63/0.3

ParameterValue
StandardsIEC EN 60947-2 Ann. B
Type of Residual CurrentType AC
Suitable ForS800S S800N S800C S800B
Rated Voltage (Ur)230 V AC 240 V AC 400 V AC
Rated Operational Voltage400/690 V
Rated Insulation Voltage (Ui)690 V
Rated Impulse Withstand Voltage (Uimp)6 kV
Rated Current (In)63 A
Rated Residual Current300 mA
Maximum Surge Current0.25 kA
Leakage Current TypeAC
Rated Frequency (f)50/60 Hz
Power Loss9 W
Number of Poles2
Operating CharacteristicInstantaneous
Options Provided-
Connecting CapacityRigid 6 … 50 mm² Flexible 6 … 70 mm²
Ambient Temperature-25...60 °C
Ambient Air TemperatureOperation -25...60 °C
Degree of ProtectionIP2X
ParameterValue
Environmental Informationdocument not needed
Short-Circuit Current Rating (SCCR)0.3 ... 0.3 A
Width in Number of Modular Spacings4.5
Product Net Width81 mm
Product Net Height108.2 mm
Product Net Depth / Length82.3 mm
Product Net Weight300 g
ETIM 8EC002297 - Residual current circuit breaker (RCCB) module
ETIM 9EC002297 - Residual current circuit breaker (RCCB) module
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2BBusiness To Business
CN885363030
eClassV11.0 : 27142210
Object Classification CodeF
Manufacturer ID2CSB802001R3630

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.