Industrial Automation Parts. Prompt replies from real people.

WAGO 787-602 24VDC

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the WAGO 787-602?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the WAGO 787-602 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
787-602
Material Number
—
Manufacturer
WAGO
Product ID
50359

Get a Free Quote

Request pricing and availability for 787-602.

More parts to source? Send your whole list in one enquiry

Key specifications

Isolation voltage (sec.-PE)
DC 0.7 kV
Series operation
Yes
Weight
300g
Nominal input voltage [V]
1 x AC 100 ... 240 V
Nominal mains frequency range
50 60 Hz;0 Hz
Nominal output current Io nom
1.3 A (24 VDC)
See all specifications

Product Highlights

  1. Input: 1-phase AC 100–240 V nominal, 90–264 VAC range, 130–300 VDC range, 50/60 Hz and 0 Hz, input current ≤ 0.3 A at 230 VAC, inrush current ≤ 25 A, passive PFC
  2. Output: 24 VDC SELV, 1.3 A nominal, deviation ≤ 3 %, residual ripple ≤ 100 mV peak-to-peak, current limitation 1.5 × Io nom typical, hiccup overload behavior, green LED 24 V OK indicator
  3. Efficiency and Losses: 83 % typical efficiency, power loss ≤ 4.9 W, maximum power loss 7 W at 90 VAC / 24 VDC / 1.3 A, mains failure hold-up time ≤ 20 ms at 230 VAC
  4. Protection and Isolation: Class I, IP20 per EN 60529, pollution degree 2, isolation voltage secondary to PE DC 0.7 kV, varistor transient suppression on primary, internal protective circuit on secondary, short-circuit-protected hiccup, open-circuit-proof, internal fuse T 2 A / 250 VAC, external DC fuse required for DC input, recommended circuit breaker C10 or B10
  5. Operating Conditions: ambient temperature -10 … +70 °C, storage -25 … +85 °C, relative humidity 30 … 85 % without condensation, derating −3 %/K above 50 °C, climatic category 3K3 per EN 60721
  6. Connection and Mounting: CAGE CLAMP® with WAGO 231 Series connectors, solid and fine-stranded conductors 0.08 … 2.5 mm² / 28 … 12 AWG, strip length 8 … 9 mm / 0.31 … 0.35 inches, DIN-35 rail mounting, dimensions 40 mm width × 90 mm height × 95 mm depth from upper DIN-rail edge, weight 300 g
  7. Operation Modes and Compliance: series operation yes, parallel operation no, CE conformity marking, EN 60950-1
787-602

Product Information

Technical Specifications

Specifications for 787-602

ParameterValue
Isolation voltage (sec.-PE)DC 0.7 kV
Protection classI
Protection typeIP20; per EN 60529
Pollution degree2
Transient suppression (primary)Varistor
Overvoltage protection; secondaryInternal protective circuit
Short-circuit-protectedYes ("hiccup")
Open-circuit-proofYes
Parallel operationNo
Series operationYes
Connection type 1Input/Output
Connection technologyCAGE CLAMP®
WAGO connectorWAGO 231 Series
Solid conductor0.08 … 2.5 mm2 / 28 12 AWG
Fine-stranded conductor0.08 … 2.5 mm2 / 28 12 AWG
Strip length8 9 mm / 0.31 0.35 inches
Note (conductor cross-section)12 AWG: THHN, THWN
Width40 mm / 1.575 inches
Height90 mm / 3.543 inches
Depth from upper-edge of DIN-rail95 mm / 3.74 inches
Mounting typeDIN-35 rail
Weight300g
Ambient temperature (operation)-10 … +70 °C
Ambient temperature (storage)-25 … +85 °C
Relative humidity30 85 % (no condensation permissible)
Derating−3 %/K (> 50 °C)
Climatic category3K3 (per EN 60721)
Conformity markingCE
Standards/specificationsEN 60950-1
Product Group6 (INTERFACE ELECTRONIC)
eCl@ss 10.027-04-07-01
eCl@ss 9.027-04-07-01
ETIM 9.0EC002540
ETIM 8.0EC002540
ECCNNO US CLASSIFICATION
PU (SPU)1 pcs
ParameterValue
Packaging typebox
Country of originDE
GTIN4045454435134
Customs tariff number8504409510
End of Sale2022-09-01
End of Production2022-09-07
End of Delivery2023-02-28
End of Service and Repair2025-02-28
RoHS Compliance StatusCompliant,No Exemption
Phases1
Nominal input voltage [V]1 x AC 100 ... 240 V
Input voltage range1 x AC 90 264 V; DC 130 300 V
Nominal mains frequency range50 60 Hz;0 Hz
Input current Ii≤ 0.3 A (230 VAC)
Inrush current≤ 25 A
Power factor correction (PFC)Passive
Mains failure hold-up time≤ 20 ms (230 VAC)
Nominal output voltage [V]DC 24 V (SELV)
Output voltage rangeDC 24 V
Default settingDC 24 V
Nominal output current Io nom1.3 A (24 VDC)
Deviation≤ 3 %
Residual ripple≤ 100 mV (peak-to-peak)
Current limitation1.5 x Io nom(typ.)
Overload behaviorHiccup
Operation status indicatorGreen LED (24 V OK)
Power loss Pl≤ 4.9 W
Power loss (max.) Pl (max.)7 W (90 VAC / 24 VDC; 1.3 A)
Efficiency (typ.)83 %
Internal fuseT 2 A / 250 VAC
Backup fusing (required)An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)Circuit breaker: C10 or B10

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp