Product Model
787-1211
Material Number
—
Manufacturer
WAGO
Product ID
50343

Get a Free Quote

Request pricing and availability for 787-1211.

More parts to source? Send your whole list in one enquiry

Key specifications

Reverse voltage protection
Yes
Series operation
Yes, for 2 devices of the same type
Weight
63g
Nominal input voltage [V]
1 x AC 100 ... 240 V
Nominal output current Io nom
5 A
Nominal output power
60W
See all specifications

Product Highlights

  1. Compact DIN-rail housing: 72 mm wide, 90 mm high, 56 mm deep (52.5 mm from upper DIN-rail edge), 63 g
  2. Electrical protection: Protection class I, overvoltage category II, pollution degree 2, primary varistor transient suppression, secondary overvoltage limited to ≤ 20 VDC in the event of a fault, reverse voltage protection
  3. Output and protection behavior: 12 VDC SELV output, 5 A / 60 W nominal, constant-power overload range 1.22–1.7 x Io nom, hiccup mode on short circuit or permanent overload, short-circuit-protected and open-circuit-proof
  4. Input: 1-phase 100–240 VAC nominal (85–264 VAC range, 125–375 VDC range), 47–63 Hz, ≤ 0.6 A input current, ≤ 30 A NTC inrush current, passive PFC
  5. Connection and installation: Push-in CAGE CLAMP® input/output with picoMAX® 5.0 (WAGO 2092 Series), 0.2–2.5 mm² / 24–12 AWG, 9–10 mm strip length, DIN-35 rail mounting, IP20 per EN 60529, UL94 V0
  6. Operating conditions: -25 to +70 °C ambient operation, -40 to +85 °C storage, 20–90 % relative humidity without condensation, derating above +45 °C at 90 VAC and above +50 °C at 230 VAC
  7. Efficiency and reliability: 88.5 % typical at 230 VAC nominal load, 87.5 % at 110 VAC nominal load, ≤ 0.6 W no-load power loss, MTBF > 500,000 h per IEC 61709
  8. Signaling and standards: Green LED DC OK operation indicator, CE conformity, EN 61204-3, RoHS compliant
787-1211

Product Information

Technical Specifications

Specifications for 787-1211

ParameterValue
Protection classI
Protection typeIP20; per EN 60529
Reverse voltage protectionYes
Overvoltage categoryII
Pollution degree2
Transient suppression (primary)Varistor
Overvoltage protection; secondary≤ 20 VDC (in the event of a fault)
Short-circuit-protectedYes
Open-circuit-proofYes
Parallel operationYes, for devices of the same type
Series operationYes, for 2 devices of the same type
MTBF> 500,000 h (per IEC 61709)
Connection type 1Input/Output
Connection technologyPush-in CAGE CLAMP®
WAGO connector picoMAX® 5.0, WAGO 2092 Series
Solid conductor0.2 2.5 m㎡/ 24 12 AWG
Fine-stranded conductor0.2 2.5 m㎡/ 24 12 AWG
Strip length9 10 mm / 0.35 0.39 inches
Cable length (max.)30 m
Width72 mm / 2.835 inches
Height90 mm / 3.543 inches
Depth56 mm / 2.205 inches
Depth from upper-edge of DIN-rail52.5 mm / 2.067 inches
Note (dimensions)Depth: 48 mm (without cover)
Housing designDIN-rail-mount enclosure
Mounting typeDIN-35 rail
Flammability class per UL94V0
Weight63g
Ambient temperature (operation)-25 … +70 °C
Ambient temperature (storage)-40 … 85 °C
Relative humidity20 90 % (no condensation permissible)
Derating-3°%/K (> +45°°C and Ue= 90°VAC); -2.3°%/K (> +50°°C and Ue= 230°VAC)
Climatic category3K3 (per EN 60721; except for low air pressure)
Conformity markingCE
Standards/specificationsEN 61204-3
ETIM 9.0EC002540
ETIM 8.0EC002540
ECCNNO US CLASSIFICATION
ParameterValue
PU (SPU)1 pcs
Packaging typebox
Country of originCN
GTIN4055143804226
Customs tariff number8504409510
RoHS Compliance StatusCompliant,No Exemption
Phases1
Nominal input voltage [V]1 x AC 100 ... 240 V
Input voltage range1 x AC 85 264 V; DC 125 375 V
Input voltage derating-2 %/V (< 100 VAC); -1.33 %/V (< 140 VDC)
Nominal mains frequency range47 63 Hz;0 Hz
Input current Ii≤ 0.6 A
Inrush current≤ 30 A (NTC)
Power factor≤ 0.5
Power factor correction (PFC)Passive
Mains failure hold-up time≤ 600 ms (230 VAC); ≤ 12 ms (110 VAC)
Nominal output voltage [V]DC 12 V (SELV)
Output voltage rangeDC 12 V
Default settingDC 12 V
Nominal output current Io nom5 A
Nominal output power60W
Deviation≤ 1 %
Deviation, dynamic load change 10 90 %≤ 1 %
Residual ripple≤ 100 mV (peak-to-peak)
Overload behaviorConstant power (in overload range: 1.22 1.7 x Io nom); Hiccup in the event of a short circuit or permanent overload
Signaling1 x LED DC OK (green)
Operation status indicatorGreen LED (Uo)
Power loss Pl≤ 0.6 W
Power loss (max.) Pl (max.)9 W (100 VAC / 12 VDC; 2.5 A)
Efficiency (typ.)88.5 % (230 VAC; Nominal load); 87.5 % (110 VAC; Nominal load)
Internal fuseT 3.15 A / 250 VAC
Backup fusing (required)An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)Circuit breaker: 6 A, 10 A or higher; Tripping characteristic: B