Industrial Automation Parts. Prompt replies from real people.

WAGO 2216-7111 Rail Chassis Terminal Blocks

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the WAGO 2216-7111?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the WAGO 2216-7111 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
2216-7111
Material Number
—
Manufacturer
WAGO
Product ID
49109

Get a Free Quote

Request pricing and availability for 2216-7111.

More parts to source? Send your whole list in one enquiry

Key specifications

Weight
25.5g
Rated voltage (III / 3)
250V
Rated impulse voltage (III / 3)
4kV
Rated current
69A
Rated current IN for specified power loss
69A
Frequency
f1= 5 Hz to f2= 150 Hz
See all specifications

Product Highlights

  1. Connection Technology: Push-in CAGE CLAMP with push-button actuation, front-entry wiring, copper conductors only, strip length 18 to 20 mm
  2. Conductor Range: Solid 0.5 to 16 mm² (20 to 6 AWG), fine-stranded 0.5 to 25 mm² (20 to 4 AWG), fine-stranded with ferrule 0.5 to 16 mm² (20 to 6 AWG)
  3. Electrical Ratings: 250 V rated voltage (III/3), 4 kV rated impulse voltage (III/3), 69 A rated current, 75 A at maximum conductor cross-section, 2.426 W power loss per pole
  4. Dimensions and Mounting: 12 mm wide, 69.4 mm high, 38.1 mm depth from upper DIN-rail edge, DIN-35 rail mounting
  5. Housing Material and Compliance: Polyamide (PA66) insulation, material group I, gray, UL94 V0 flammability, RoHS compliant with no exemption, ratings per IEC/EN 60947-7-1
  6. Temperature Range: Processing -35 to +85 °C, continuous operating -60 to +105 °C
  7. Railway Suitability: Tested to DIN EN 50155, DIN EN 61373 shock and vibration (Category 1, Class A/B, 5 to 150 Hz, 5 g, 30 ms half-sine shock), passed contact-fault monitoring and voltage-drop checks
  8. Configuration: 1 clamping unit, 1 potential, 1 level, 2 jumper slots, center/side marking level
2216-7111

Product Information

Technical Specifications

Specifications for 2216-7111

ParameterValue
Clamping units1
Total number of potentials1
Number of levels1
Number of jumper slots2
Width12 mm / 0.472 inches
Height69.4 mm / 2.732 inches
Depth from upper-edge of DIN-rail38.1 mm / 1.5 inches
Mounting typeDIN-35 rail
Marking levelCenter/side marking
Note (material data)Information on material specifications can be found here
Colorgray
Material groupI
Insulation material (main housing)Polyamide (PA66)
Flammability class per UL94V0
Fire load0.411MJ
Weight25.5g
Processing temperature-35 … +85 °C
Continuous operating temperature-60 … +105 °C
ETIM 9.0EC001257
ETIM 8.0EC001257
ECCNNO US CLASSIFICATION
PU (SPU)25 pcs
Packaging typeBox
Country of originPL
GTIN4066966309669
Customs tariff number85369095000
RoHS Compliance StatusCompliant,No Exemption
Ratings perIEC/EN 60947-7-1
Rated voltage (III / 3)250V
Rated impulse voltage (III / 3)4kV
Rated current69A
Current at conductor cross-section (max.) mm275A
Legend (ratings)(III3) ≙ Overvoltage category IIIPollution degree 3
Power loss, per pole (potential)2.426W
Rated current IN for specified power loss69A
ParameterValue
Connection technologyPush-in CAGE CLAMP®
Actuation typePush-button
Connectable conductor materialsCopper
Nominal cross-section16 mm2
Solid conductor0.5 16 m㎡/ 20 6 AWG
Solid conductor; push-in termination6 16 m㎡/ 14 6 AWG
Fine-stranded conductor0.5 25 m㎡/ 20 4 AWG
Fine-stranded conductor; with insulated ferrule0.5 16 m㎡/ 20 6 AWG
Fine-stranded conductor; with ferrule; push-in termination6 16 m㎡/ 10 6 AWG
Note (conductor cross-section)Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.AWG specifications were converted according to IEC.
Strip length18 20 mm / 0.71 0.79 inches
Wiring directionFront-entry wiring
Test specification <br/>Railway applications <br/>Rolling stock <br/>Electronic equipmentDIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications <br/>Rolling stock equipment <br/>Shock and vibration testsDIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation locationService life test, Category 1, Class A/B
Function test with noise-like vibrationTest passed according to Section 8 of the standard
Frequencyf1= 5 Hz to f2= 150 Hz
Acceleration5g (highest test level used for all axes)
Test duration per axis5 h
Test directionsX, Y and Z axes
Monitoring for contact faults/interruptionsPassed
Voltage drop measurement before and after each axisPassed
Simulated service life test through increased levels of noise-like vibrationTest passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptionsPassed
Extended test scope: Voltage drop measurement before and after each axisPassed
Shock testTest passed according to Section 10 of the standard
Shock formHalf sine
Shock duration30 ms
Number of shocks per axis3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipmentPassed

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp