| Note | The analog input module must only be operated via 24 VDC Ex i!General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals! |
|---|
| Order text | 2-Channel Analog Input; TC |
|---|
| Number of analog inputs | 2 |
|---|
| Number of Channels | 2 |
|---|
| Signal type | Thermocouple |
|---|
| Signal type (configurable) | Yes |
|---|
| Sensor connection | 2 x (2-wire) |
|---|
| Sensor types | Thermocouple K; Configurable: J, B, E, L, N, R, S, T, U, C; Voltage sensor: ±30 mV, ±60 mV, ±120 mV |
|---|
| Temperature range | Type-dependent from ?100 to +1,800 °C |
|---|
| Measurement range | Thermocouples:Type B: +600 +1.800 °C; Type E: 00 +1.000 °C; Type J: 00 +1.200 °C; Type K: 00 +1.370 °C* *(default setting); Type L: -100 … +900 °C; Type N: 00 +1.300 °C; Type R: 0 +1.700 °C; Type S: 0 +1.700 °C; Type T: 00 … +400 °C; Type U: -25 … +600 °C;Voltage sensors:MB1: ±30 mV; MB2: ±60 mV; MB3: ±120 mV |
|---|
| Resolution (over entire range) | 0.1 °C or 0.01 mV for voltage measurement |
|---|
| Conversion time (typ. ≤ | 320ms |
|---|
| Conversion time | ≤ 320 ms (both channels) |
|---|
| Measurement error (25 °C) | < ±6 K (voltage input < ±2 K; cold junction compensation < ±4 K) |
|---|
| Temperature coefficient | < ± 0.2 K / K of the largest output area (type K) |
|---|
| Cold junction compensation | internal; at each pair of terminal blocks |
|---|
| Internal resistance | 1000kΩ |
|---|
| Intrinsically safe Ex i | Yes |
|---|
| Data width | 2 x 16-bit data; 2 x 8-bit control/status (optional) |
|---|
| Configuration options | WAGO-I/O-CHECK |
|---|
| Supply voltage (system) | 5 VDC; via data contacts |
|---|
| Current consumption (5 V system supply) | 13.5mA |
|---|
| Supply voltage (field) | 24 VDC; (Ex i power supply: Uo= max. 27.3 V); via power jumper contacts (power supply via blade contact; transmission via spring contact) |
|---|
| Current consumption, field supply (module with no external load) | 8.5mA |
|---|
| Power consumption Pmax. | 0.3 W (max.) |
|---|
| Power loss Pl | 0.3 W (max.) |
|---|
| Isolation | 300 VAC system/supply |
|---|
| Number of incoming power jumper contacts | 2 |
|---|
| Number of outgoing power jumper contacts | 2 |
|---|
| Indicators | LED (A, E) green: Function AI 1, AI 2; LED (B, F) red: Error AI 1, AI 2 |
|---|
| Identification | ATEXII 3 (1) G Ex ec [ia Ga] IIC T4 GcII (1) D [Ex ia Da] IIICI (M1) [Ex ia Ma] I |
|---|
| Ex standard | EN IEC 60079-0, -7, -11 |
|---|
| Safety-relevant data (circuit) | Uo= 14.4 V; Io= 29.1 mA; Po= 52.4 mW; linear characteristic curve |
|---|
| Reactances Ex ia IIC | Lo= 52 mH; Co= 650 nF |
|---|
| Reactances Ex ia IIB | Lo= 100 mH; Co= 4.0 µF |
|---|
| Reactances Ex ia IIA | Lo= 300 mH; Co= 15.8 µF |
|---|
| Reactances Ex ia I | Lo= 400 mH; Co= 17.9 µF |
|---|
| Reactances (note) | Reactances without accounting for the concurrence of capacitance (Co) and inductance (Lo) |
|---|
| Connection technology: inputs / outputs | 8 x CAGE CLAMP® |
|---|
| Connection type 1 | Inputs/outputs |
|---|
| Solid conductor | 0.08 2.5 mm2 / 28 14 AWG |
|---|
| Fine-stranded conductor | 0.08 2.5 mm2 / 28 14 AWG |
|---|
| Strip length | 8 9 mm / 0.31 0.35 inches |
|---|
| Width | 24 mm / 0.945 inches |
|---|
| Height | 100 mm / 3.937 inches |
|---|
| Depth | 67.8 mm / 2.669 inches |
|---|
| Depth from upper-edge of DIN-rail | 60.6 mm / 2.386 inches |
|---|
| Mounting type | DIN-35 rail |
|---|