- 855-305/600-509
WAGO 855-305/600-509 inductive plug-in current transformer for current measurement. Primary rated current 600 A, secondary rated current 5 A, rated power Sr 5 VA, accuracy class 0.5, rated frequency 50 … 60 Hz. Closed current transformer with Ø 26 mm feedthrough for the measurement conductor and CAGE CLAMP connection technology; strip length 9 10 mm, solid and fine-stranded conductors 0.08 4 mm² (28 12 AWG). Highest voltage for equipment Um AC 1.2 kVrms; test voltage AC 6 kV, 50 Hz, 1 min. Rated continuous thermal current Icth AC 1.2 x IN; rated short-time thermal current Ith 60 x IN/ 1 s (max. 100 kA / 1 s). Insulation class E. Dimensions 60 mm wide, 80.9 mm high, 52 mm deep; weight 230 g. Ambient temperature -5 … +50 °C operation, -25 … +70 °C storage; maximum operating altitude 1000 m. Standards/specifications: EN 61869-1. Conformity marking: CE.
- 855-4001/100-001
WAGO 855-4001/100-001 split-core current transformer for current measurement, with a 100 A primary rated current and 1 A secondary rated current, accuracy class 1, and rated power 0.2 VA. Rated frequency is 50 to 60 Hz. The split-core design allows installation without interrupting the measuring cable. The measurement conductor feedthrough is Ø 18 mm. The unit measures 57.2 mm wide, 67 mm high, and 49 mm deep, weighs 412 g, and is suspended. It has a 3 m cable, 2 x 0.5 mm2 fine-stranded, with brown = S1 and blue = S2. Protection type IP20; highest voltage for equipment Um AC 720 Vrms; test voltage AC 3 kV, 50 Hz, 1 min. Operating ambient temperature -10 to +55 °C; storage -20 to +70 °C; relative humidity 5 to 85 % without condensation; maximum operating altitude 2000 m. Conforms to EN 61869-1; CE marking.
- 855-4001/150-001
WAGO 855-4001/150-001 split-core current transformer, suspended mounting, for current measurement. Primary rated current 150 A, secondary rated current 1 A, rated power 0.2 VA, accuracy class 1, rated frequency 50 to 60 Hz. Feedthrough for measurement conductor Ø 18 mm. Cable: 2 x 0.5 mm2 fine-stranded, 3 m, brown = S1, blue = S2. Highest voltage for equipment Um AC 720 Vrms; test voltage AC 3 kV, 50 Hz, 1 min. Rated continuous thermal current 100%, rated short-time thermal current 60 x IN / 1 s, rated surge current 2.5 x Ith. IP20. Dimensions 57.2 mm x 67 mm x 49 mm; weight 416 g. Operating temperature -10 to +55 °C, storage -20 to +70 °C, relative humidity 5 to 85% without condensation, maximum operating altitude 2000 m. Conformity marking CE; standards/specifications EN 61869-1.
- 855-4001/200-001
WAGO 855-4001/200-001 split-core current transformer, suspended mounting, for current measurement. Primary rated current 200 A, secondary rated current 1 A, rated frequency 50 … 60 Hz, rated power Sr 0.2 VA, accuracy class 0.5. Rated continuous thermal current Icth 100%, rated short-time thermal current Ith 60 x IN/ 1 s, rated surge current Idyn 2.5 x Ith. Highest voltage for equipment Um AC 720 Vrms; test voltage AC 3 kV, 50 Hz, 1 min. Feedthrough for measurement conductor Ø 18 mm. 3 m cable, 2 x 0.5 mm2 fine-stranded, brown = S1, blue = S2. Dimensions 57.2 mm x 67 mm x 49 mm; weight 400 g. IP20. Ambient temperature -10 … +55 °C operation, -20 … +70 °C storage; relative humidity 5 85% without condensation; operating altitude max. 2000 m. CE marking; EN 61869-1.
- 855-4005/150-101
WAGO 855-4005/150-101 split-core current transformer, suspended mounting, for current measurement. Primary rated current 150 A, secondary rated current 5 A, rated power 1 VA, accuracy class 1, rated frequency 50 to 60 Hz. Highest voltage for equipment Um AC 720 Vrms; test voltage AC 3 kV at 50 Hz for 1 min. Measured conductor feedthrough Ø 18 mm. Connection cable 2 x 1.5 mm² fine-stranded, 0.5 m, color code black = S1, red = S2. Rated continuous thermal current Icth 100%, rated short-time thermal current Ith 60 x IN for 1 s, rated surge current Idyn 2.5 x Ith. Dimensions 57.2 x 67 x 49 mm, 341 g. IP20. Operating temperature -10 to +55 °C, storage -20 to +70 °C, relative humidity 5 to 85% without condensation, maximum operating altitude 2000 m. CE, EN 61869-1, RoHS compliant.
- 855-401/400-501
WAGO 855-401/400-501 is a closed current transformer with a 400 A primary rated current and 1 A secondary rated current, rated power 5 VA, accuracy class 1, and rated frequency 50 to 60 Hz. It has a Ø 32 mm feedthrough for the measurement conductor and uses CAGE CLAMP connection technology, accepting 0.08 to 4 mm² (28 to 12 AWG) solid or fine-stranded conductors with a 9 to 10 mm strip length. Dimensions are 70 mm wide, 91.15 mm high, and 52 mm deep; weight is 230 g. Test voltage is AC 6 kV at 50 Hz for 1 min, highest voltage for equipment Um is AC 1.2 kVrms, insulation class E, conforming to EN 61869-1, with CE marking. Operating ambient temperature is -5 to +50 °C, storage -25 to +70 °C, maximum operating altitude 1000 m.
- 855-405/200-209
WAGO 855-405/200-209 is a closed current transformer with a Ø 32 mm feedthrough for the measurement conductor. It measures current with a 200 A primary rated current and 5 A secondary rated current, accuracy class 0.5, rated power 2.5 VA, and rated frequency 50 … 60 Hz. Rated continuous thermal current is AC 1.2 x IN; rated short-time thermal current is 60 x IN/1 s (max. 100 kA/1 s). Test voltage is AC 6 kV; 50 Hz; 1 min, and highest voltage for equipment Um is AC 1.2 kVrms. Dimensions are 70 mm width, 91.15 mm height, and 52 mm depth, weight 259 g. Operation is rated -5 … +50 °C, storage -25 … +70 °C, maximum operating altitude 1000 m. Connection uses CAGE CLAMP® with 9 10 mm strip length, accepting 0.08 4 mm2 / 28 12 AWG solid and fine-stranded conductors. Standards/specifications: EN 61869-1; CE marking.
- 855-405/250-209
WAGO 855-405/250-209 plug-in current transformer, closed-type, for current measurement. Primary rated current 250 A, secondary rated current 5 A, rated power Sr 2.5 VA, accuracy class 0.5, rated frequency 50 … 60 Hz. Rated continuous thermal current Icth AC 1.2 x IN; rated short-time thermal current Ith 60 x IN/1 s (max. 100 kA/1 s). Overcurrent limiting factor FS5/FS10 (type dependent; see type plate inscription). Highest voltage for equipment Um AC 1.2 kVrms; test voltage AC 6 kV, 50 Hz, 1 min. Feedthrough for measurement conductor Ø 32 mm. Insulation class E. CAGE CLAMP connection, strip length 9 10 mm, solid and fine-stranded conductors 0.08 4 mm2 (28 12 AWG). Dimensions 70 x 91.15 x 52 mm; weight 280 g. Operating temperature -5 … +50 °C, storage -25 … +70 °C, max. operating altitude 1000 m. Conforms to EN 61869-1, CE marked.