Industrial Automation Parts. Prompt replies from real people.

WAGO 2606-3101 PCB Terminal Block

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the WAGO 2606-3101?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the WAGO 2606-3101 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
2606-3101
Material Number
—
Manufacturer
WAGO
Product ID
41085

Get a Free Quote

Request pricing and availability for 2606-3101.

More parts to source? Send your whole list in one enquiry

Key specifications

Weight
5g
Continuous operating temperature
-60 … +105 °C
Rated voltage (III / 3)
1000V
Rated impulse voltage (III / 3)
8kV
Rated current
41A
Frequency
f1= 5 Hz to f2= 150 Hz
See all specifications

Product Highlights

  1. Connection Technology: Push-in CAGE CLAMP with lever actuation, accepts solid and fine-stranded conductors from 0.2 to 10 mm² (24 to 8 AWG), strip length 11 to 13 mm
  2. Configuration: Single-pole PCB terminal block with one potential, one clamping unit, one level, and two solder pins per potential
  3. PCB Mounting: THT solder pins arranged in-line, pin spacing 7.5 mm, solder pin length 4 mm, solder pin dimensions 1.5 x 1.2 mm, drilled hole diameter 2(+0.1) mm, conductor connection direction to PCB 90°
  4. Dimensions: Width 10.35 mm, height 31 mm, height from surface 27 mm, depth 24 mm
  5. Materials and Temperature Range: Gray polyamide (PA66) housing, chrome-nickel spring steel clamping spring, electrolytic copper contacts with tin plating, UL94 V0 flammability class, continuous operating temperature -60 to +105 °C
  6. Ratings: IEC/EN 60664-1 rated voltage 1000 V, rated impulse voltage 8 kV, rated current 41 A, UL and CSA rated voltage 600 V and rated current 31 A for Use Groups B and C
  7. Mechanical Stress Protection: Single-pole terminal block stability is lower than that of a multi-pole terminal strip, so protection against excessive mechanical stress such as torsional or bending stress must be ensured during conductor connection and subsequent use, for example by additional support, briefly holding the connected conductor, and appropriate actuation instructions
2606-3101

Product Information

Technical Specifications

Specifications for 2606-3101

ParameterValue
NoteThe inherent stability of a single-pole PCB terminal block is less than that of a multi-pole terminal strip. The customer must therefore ensure that these terminal blocks are protected against excessive mechanical stress (e.g., torsional or bending stress), both when connecting the conductor and during subsequent use, for example by providing additional support, shortly holding the connected conductor and appropriate actuation instructions.
Variants:Other pole numbers
Clamping units1
Total number of potentials1
Number of connection types1
Number of levels1
Pin spacing7.5 mm / 0.295 inches
Width10.35 mm / 0.407 inches
Height31 mm / 1.22 inches
Height from the surface27 mm / 1.063 inches
Depth24 mm / 0.945 inches
Solder pin length4mm
Solder pin dimensions1.5 x 1.2 mm
Drilled hole diameter with tolerance2(+0.1)mm
PCB contactTHT
Solder pin arrangementOver the entire terminal strip (in-line)
Number of solder pins per potential2
Note (material data)Information on material specifications can be found here
Colorgray
Material groupI
Insulation material (main housing)Polyamide (PA66)
Flammability class per UL94V0
Clamping spring materialChrome-nickel spring steel (CrNi)
Contact materialElectrolytic copper (ECu)
Contact platingTin
Fire load0.035MJ
Actuator colororange
Weight5g
Limit temperature range-60 … +105 °C
Processing temperature-35 … +60 °C
Continuous operating temperature-60 … +105 °C
eCl@ss 10.027-44-04-01
eCl@ss 9.027-44-04-01
ETIM 9.0EC002643
ETIM 8.0EC002643
ECCNNO US CLASSIFICATION
PU (SPU)200 pcs
Packaging typebox
Country of originPL
GTIN4055143586580
Customs tariff number8536904000
RoHS Compliance StatusCompliant,No Exemption
Ratings perIEC/EN 60664-1
Rated voltage (III / 3)1000V
Rated impulse voltage (III / 3)8kV
Rated voltage (III/2)1000V
Rated surge voltage (III/2)8kV
Nominal voltage (II/2)1000V
ParameterValue
Rated surge voltage (II/2)8kV
Rated current41A
Legend (ratings)(III2) ≙ Overvoltage category IIIPollution degree 2
Approvals perCSA
Rated voltage UL (Use Group B)600V
Rated current UL (Use Group B)31A
Rated voltage UL (Use Group C)600V
Rated current UL (Use Group C)31A
Rated voltage CSA (Use Group B)600V
Rated current CSA (Use Group B)31A
Rated voltage CSA (Use Group C)1000V
Rated current CSA (Use Group C)31A
Connection technologyPush-in CAGE CLAMP®
Actuation typeLever
Solid conductor0.2 10 m㎡/ 24 8 AWG
Fine-stranded conductor0.2 10 m㎡/ 24 8 AWG
Fine-stranded conductor; with insulated ferrule0.25 6 mm2
Fine-stranded conductor; with uninsulated ferrule0.25 6 mm2
Fine-stranded conductor; with twin ferrule0.25 2.5 mm2
Strip length11 13 mm / 0.43 0.51 inches
Conductor connection direction to PCB90°
Number of poles1
Test specification <br/>Railway applications <br/>Rolling stock <br/>Electronic equipmentDIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications <br/>Rolling stock equipment <br/>Shock and vibration testsDIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation locationService life test, Category 1, Class A/B
Function test with noise-like vibrationTest passed according to Section 8 of the standard
Frequencyf1= 5 Hz to f2= 150 Hz
Acceleration5g (highest test level used for all axes)
Test duration per axis5 h
Test directionsX, Y and Z axes
Monitoring for contact faults/interruptionsPassed
Voltage drop measurement before and after each axisPassed
Simulated service life test through increased levels of noise-like vibrationTest passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptionsPassed
Extended test scope: Voltage drop measurement before and after each axisPassed
Shock testTest passed according to Section 10 of the standard
Shock formHalf sine
Shock duration30 ms
Number of shocks per axis3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipmentPassed