Industrial Automation Parts. Prompt replies from real people.

Schneider LC1G630EHEA Electric

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the Schneider LC1G630EHEA?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1G630EHEA cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1G630EHEA
Material Number
—
Manufacturer
Schneider
Product ID
38714

Get a Free Quote

Request pricing and availability for LC1G630EHEA.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current
1050 A (at <40 °C) at <= 1000 V AC-1 / 630 A (at <60 °C) at <= 440 V AC-3
[Uc] control circuit voltage
48...130 V AC 50/60 Hz / 48...130 V DC
IP degree of protection
IP2X front face with shrouds conforming to IEC 60529 / IP2X front face with shrouds conforming to VDE 0106
See all specifications

Product Highlights

  1. Power Switching Capacity: 3-pole contactor rated up to 1000 V AC 50/60 Hz and 460 V DC, with 1050 A AC-1 at 40 °C and 630 A AC-3 at 60 °C
  2. Motor Power Range: 180 to 500 kW AC-3e and AC-3 depending on voltage from 230 to 1000 V AC, and 250 to 700 hp at 200/208 to 575/600 V 60 Hz
  3. Control Circuit: 48 to 130 V AC 50/60 Hz or DC coil with built-in bidirectional peak limiting, 40 to 70 ms closing and 15 to 50 ms opening
  4. Contacts and Terminals: 3 NO power poles plus 1 NO and 1 NC auxiliary contacts, bar or lug-ring power connections and push-in control connections
  5. Durability and Safety: 5 million mechanical cycles, B10d of 100000 cycles with nominal load and 1800000 cycles with mechanical load per EN/ISO 13849-1
  6. Standards and Protection: EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1 and other listed standards, IP2X front face with shrouds, operating ambient -25 to 60 °C
LC1G630EHEA

Product Information

Technical Specifications

Specifications for LC1G630EHEA

ParameterValue
Product or component typeContactor
Range of productTeSys Giga
[Ue] rated operational voltage<= 1000 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current1050 A (at <40 °C) at <= 1000 V AC-1 / 630 A (at <60 °C) at <= 440 V AC-3
[Uc] control circuit voltage48...130 V AC 50/60 Hz / 48...130 V DC
Control circuit voltage limitsOperational: 0.8 Uc Min...1.1 Uc Max (at <60 °C) / Drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)
Power dissipation per pole70 W AC-1 - Ith 1050 A / 26 W AC-3 - Ith 630 A
Connections - terminalsPower circuit: bar 2 - busbar cross section: 52 x 20 mmPower circuit: lugs-ring terminals 1 185 mm²Power circuit: bolted connectionControl circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable endControl circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable endControl circuit: push-in 2 0.5…1.0 mm² with cable endControl circuit: push-in 0.75…2.5 mm² - cable stiffness: solid stranded without cable endControl circuit: push-in 0.75…2.5 mm² - cable stiffness: flexible with cable end
ParameterValue
Connection pitch70 mm
Height388.5 mm
Width211 mm
Depth266 mm
IP degree of protectionIP2X front face with shrouds conforming to IEC 60529 / IP2X front face with shrouds conforming to VDE 0106
Ambient air temperature for operation-25…60 °C
Product certificationsCB SchemeCCCcULusEACCEUKCAEU-RO-MR by DNV-GL