LC1G4004EHEA
Material Number
—
Manufacturer
Schneider
Product ID
38686

Get a Free Quote

Request pricing and availability for LC1G4004EHEA.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current
400 A (at <60 °C) at <= 440 V AC-3 / 550 A (at <40 °C) at <= 1000 V AC-1
[Uc] control circuit voltage
48...130 V AC 50/60 Hz / 48...130 V DC
IP degree of protection
IP2X front face with shrouds conforming to IEC 60529 / IP2X front face with shrouds conforming to VDE 0106
See all specifications

Product Highlights

  1. Rated operational current: 400 A at up to 440 V AC-3 at 60 °C and 550 A at up to 1000 V AC-1 at 40 °C
  2. Poles: 4P, 4 NO power poles plus 1 NO + 1 NC auxiliary contacts
  3. Control circuit voltage: 48 to 130 V AC 50/60 Hz or 48 to 130 V DC, with operational limits 0.8 to 1.1 Uc and drop-out 0.1 to 0.45 Uc at 60 °C
  4. Utilisation categories: AC-3, AC-3e, AC-1, AC-5a, AC-5b, AC-6a, AC-6b, DC-1, DC-3 and DC-5
  5. Rated operational voltage: up to 1000 V AC 50/60 Hz or up to 460 V DC
  6. Short-time withstand current: 3.6 kA for 10 s, 2.4 kA for 30 s, 1.7 kA for 1 min, 1.2 kA for 3 min and 1.0 kA for 10 min
  7. Mechanical durability: 8 million cycles, with B10d of 400000 cycles at nominal load and 3000000 cycles at mechanical load per EN/ISO 13849-1
  8. Coil: built-in bidirectional peak limiting, 450 VA inrush and 11.7 VA hold-in at 50/60 Hz AC, 360 W inrush and 8.3 W hold-in DC
  9. Operating time: 40 to 70 ms closing and 15 to 50 ms opening
  10. Power connections: 32 x 10 mm busbar, 185 mm² ring lugs or bolted connection, 45 mm connection pitch, 35 N·m tightening torque
  11. Standards and certifications: EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, JIS C8201-5-1, UL 60335-1, UL 60335-2-40 Annex JJ, CB Scheme, CCC, cULus, EAC, CE, UKCA and EU-RO-MR by DNV-GL
  12. Ambient air temperature: -25 to 60 °C operation, -60 to 80 °C storage and -40 to 70 °C around the device at Uc
LC1G4004EHEA

Product Information

Technical Specifications

Specifications for LC1G4004EHEA

ParameterValue
Product or component typeContactor
Range of productTeSys Giga
[Ue] rated operational voltage<= 1000 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current400 A (at <60 °C) at <= 440 V AC-3 / 550 A (at <40 °C) at <= 1000 V AC-1
[Uc] control circuit voltage48...130 V AC 50/60 Hz / 48...130 V DC
Control circuit voltage limitsOperational: 0.8 Uc Min...1.1 Uc Max (at <60 °C) / Drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)
Power dissipation per pole30 W AC-1 - Ith 550 A / 16 W AC-3 - Ith 400 A
Connections - terminalsPower circuit: bar 2 - busbar cross section: 32 x 10 mmPower circuit: lugs-ring terminals 1 185 mm²Power circuit: bolted connectionControl circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable endControl circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable endControl circuit: push-in 2 0.5…1.0 mm² with cable endControl circuit: push-in 0.75…2.5 mm² - cable stiffness: solid stranded without cable endControl circuit: push-in 0.75…2.5 mm² - cable stiffness: flexible with cable end
ParameterValue
Connection pitch45 mm
Height290 mm
Width185 mm
Depth226 mm
IP degree of protectionIP2X front face with shrouds conforming to IEC 60529 / IP2X front face with shrouds conforming to VDE 0106
Ambient air temperature for operation-25…60 °C
Product certificationsCB SchemeCCCcULusEACCEUKCAEU-RO-MR by DNV-GL