Q1Can you supply the Schneider LC2K090047E72?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC2K090047E72 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC2K090047E72
Material Number
—
Manufacturer
Schneider
Product ID
38678

Get a Free Quote

Request pricing and availability for LC2K090047E72.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: 690 V AC 50/60 Hz
[Ie] rated operational current
20 A (at <50 °C) at <= 440 V AC AC-1 for power circuit / 16 A (at <70 °C) at 690 V AC AC-1 for power circuit
[Uc] control circuit voltage
48 V AC 50/60 Hz
IP degree of protection
IP20 conforming to VDE 0106
See all specifications

Product Highlights

  1. Standards and certifications: Compliant with IEC 60947, VDE 0660, BS 5424 and NF C 63-110, certified by CB Scheme, CCC, UL, CSA, EAC, CE and UKCA
  2. Rated operational voltage and current: Power circuit 690 V AC 50/60 Hz, 20 A at up to 440 V AC (AC-1) at 50 °C and 16 A at 690 V AC (AC-1) at 70 °C
  3. Making and breaking capacity: 110 A AC making capacity for power circuit conforming to NF C 63-110 and IEC 60947, breaking capacity 110 A at 220 to 440 V and 70 A at 660 to 690 V conforming to IEC 60947
  4. Control circuit: AC 50/60 Hz with 48 V AC control circuit voltage, built-in bidirectional peak limiting diode suppressor, 30 VA inrush power and 4.5 VA hold-in power consumption at 20 °C
  5. Contact configuration and durability: 4P changeover contactor with 4 NO power poles, mechanical durability 5 Mcycles and electrical durability 0.18 Mcycles at 20 A AC-1 up to 440 V
LC2K090047E72

Product Information

Technical Specifications

Specifications for LC2K090047E72

ParameterValue
Product or component typeChangeover contactor
[Ue] rated operational voltagePower circuit: 690 V AC 50/60 Hz
[Ie] rated operational current20 A (at <50 °C) at <= 440 V AC AC-1 for power circuit / 16 A (at <70 °C) at 690 V AC AC-1 for power circuit
[Uc] control circuit voltage48 V AC 50/60 Hz
Control circuit voltage limitsOperational: 0.8...1.15 Uc (at <50 °C) / Drop-out: 0.2...0.75 Uc (at <50 °C)
power pole contact composition4 NO
RangeTeSys
Product nameTeSys K
ParameterValue
Connections - terminalsFaston terminals 2 cable(s) - busbar cross section: 2.8 mm / Faston terminals 1 cable(s) - busbar cross section: 6.35 mm
Height58 mm
Width90 mm
Depth57 mm
IP degree of protectionIP20 conforming to VDE 0106
Ambient air temperature for operation-25…50 °C
Product certificationsCB SchemeCCCULCSAEACCEUKCA

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.