Industrial Automation Parts. Prompt replies from real people.

Schneider LC1K0610Q7 TeSys K Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the Schneider LC1K0610Q7?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1K0610Q7 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1K0610Q7
Material Number
—
Manufacturer
Schneider
Product ID
38466

Get a Free Quote

Request pricing and availability for LC1K0610Q7.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 690 V AC <= 400 Hz / Signalling circuit: <= 690 V AC <= 400 Hz
[Ie] rated operational current
6 A (at <60 °C) at <= 440 V AC AC-3 for power circuit / 6 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage
380...400 V AC 50/60 Hz
IP degree of protection
IP2X conforming to VDE 0106
See all specifications

Product Highlights

  1. Product Type: TeSys LC1K contactor for control and motor control applications
  2. Utilisation Category: AC-3, AC-3e, and AC-4
  3. Pole Configuration: 3 poles with 3 NO power pole contacts and 1 NO instantaneous auxiliary contact
  4. Rated Operational Voltage: Power and signalling circuits up to 690 V AC at up to 400 Hz
  5. Rated Operational Current: 6 A at up to 60 °C at up to 440 V AC for AC-3 and AC-3e power circuits
  6. Control Circuit: AC 50/60 Hz with 380 to 400 V AC control circuit voltage
  7. Motor Power Ratings: 1.5 kW at 220 to 230 V AC, 2.2 kW at 380 to 415 V AC, and 3 kW at 440/690 V AC for AC-3, AC-3e, and AC-4
  8. Rated Impulse Withstand Voltage: 8 kV
LC1K0610Q7

Product Information

Technical Specifications

Specifications for LC1K0610Q7

ParameterValue
Product or component typeContactor
[Ue] rated operational voltagePower circuit: <= 690 V AC <= 400 Hz / Signalling circuit: <= 690 V AC <= 400 Hz
[Ie] rated operational current6 A (at <60 °C) at <= 440 V AC AC-3 for power circuit / 6 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage380...400 V AC 50/60 Hz
Control circuit voltage limitsOperational: 0.8...1.15 Uc (at <50 °C) / Drop-out: >= 0.20 Uc (at <50 °C)
power pole contact composition3 NO
RangeTeSys
Device short nameLC1K
ParameterValue
Connections - terminalsScrew clamp terminals 1 cable(s) 1.5…4 mm²solidScrew clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable endScrew clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable endScrew clamp terminals 2 cable(s) 1.5…4 mm²solidScrew clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable endScrew clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end
Height58 mm
Width45 mm
Depth57 mm
IP degree of protectionIP2X conforming to VDE 0106
Ambient air temperature for storage-50…80 °C
Product certificationsCB SchemeCCCULCSAEACCEUKCA

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp