Industrial Automation Parts. Prompt replies from real people.

Schneider LC1K06107T7 TeSys K 3P AC-3 Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the Schneider LC1K06107T7?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1K06107T7 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1K06107T7
Material Number
—
Manufacturer
Schneider
Product ID
38449

Get a Free Quote

Request pricing and availability for LC1K06107T7.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: 690 V AC 50/60 Hz / Signalling circuit: <= 690 V AC 50/60 Hz
[Ie] rated operational current
6 A at <= 440 V AC AC-3 for power circuit
[Uc] control circuit voltage
type instantaneous 1 NO
IP degree of protection
IP2X conforming to VDE 0106
See all specifications

Product Highlights

  1. Motor Control: 3-pole contactor with 3 NO power poles and 1 NO auxiliary contact, rated 6 A at up to 440 V AC in AC-3, for motor control up to 3 kW at 440 to 690 V AC
  2. Control Circuit: 480 V AC 50/60 Hz coil with operational range 0.8 to 1.15 Uc and drop-out range 0.2 to 0.75 Uc at up to 50 °C
  3. Durability: 10 million mechanical cycles, 1.3 million electrical cycles at 6 A AC-3 up to 440 V, maximum operating rate 3600 cycles per hour
  4. Insulation and Voltage: Rated insulation voltage 690 V IEC and 600 V UL/CSA, rated impulse withstand voltage 8 kV, overvoltage category III
  5. Terminals and Mounting: Faston terminals 2 x 2.8 mm and 1 x 6.35 mm, plate or rail mounting, IP2X protection
  6. Standards: EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, GB/T 14048.4
LC1K06107T7

Product Information

Technical Specifications

Specifications for LC1K06107T7

ParameterValue
Product or component typeContactor
Range of productTeSys K
[Ue] rated operational voltagePower circuit: 690 V AC 50/60 Hz / Signalling circuit: <= 690 V AC 50/60 Hz
[Ie] rated operational current6 A at <= 440 V AC AC-3 for power circuit
[Uc] control circuit voltagetype instantaneous 1 NO
Control circuit voltage limitsOperational: 0.8...1.15 Uc (at <50 °C) / Drop-out: 0.2...0.75 Uc (at <50 °C)
[Uc] control circuit voltage480 V AC 50/60 Hz
RangeTeSys
ParameterValue
Connections - terminalsFaston terminals 2 cable(s) - busbar cross section: 2.8 mm / Faston terminals 1 cable(s) - busbar cross section: 6.35 mm
Height58 mm
Width45 mm
Depth57 mm
IP degree of protectionIP2X conforming to VDE 0106
Ambient air temperature for storage-50…80 °C
Product certificationsCB SchemeCCCULCSAEACCEUKCA

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp