Q1Can you supply the Schneider LC1K09103B7?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1K09103B7 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1K09103B7
Material Number
—
Manufacturer
Schneider
Product ID
38433

Get a Free Quote

Request pricing and availability for LC1K09103B7.

More parts to source? Send your whole list in one enquiry

Key specifications

Product or component type
Contactor
[Ue] rated operational voltage
Power circuit: <= 690 V AC <= 400 Hz / Signalling circuit: <= 690 V AC <= 400 Hz
[Ie] rated operational current
9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit / 9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit / 20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit
[Uc] control circuit voltage
24 V AC 50/60 Hz
Control circuit voltage limits
Operational: 0.8...1.15 Uc (at <50 °C) / Drop-out: >= 0.20 Uc (at <50 °C)
power pole contact composition
3 NO
See all specifications

Product Highlights

  1. Motor Switching Capacity: 4 kW at 380...415 V AC and 440/690 V AC in AC-3, AC-3e, and AC-4, and 2.2 kW at 220...230 V AC
  2. Current Ratings: 9 A AC-3/AC-3e and 20 A AC-1 at up to 440 V AC and 690 V AC respectively, with 16 A conventional thermal current for the power circuit
  3. Control Circuit: 24 V AC 50/60 Hz coil with 30 VA inrush and 4.5 VA hold-in power, operational from 0.8 to 1.15 Uc
  4. Contact Configuration: 3 NO power poles and 1 NO instantaneous auxiliary contact
  5. Durability: 10 million mechanical cycles and 1.3 million electrical cycles at 9 A AC-3 up to 440 V
  6. Mounting and Terminals: Plate or rail mounting with spring terminals accepting 0.75 to 1.5 mm² solid or flexible conductors
LC1K09103B7

Product Information

Technical Specifications

Specifications for LC1K09103B7

ParameterValue
Product or component typeContactor
[Ue] rated operational voltagePower circuit: <= 690 V AC <= 400 Hz / Signalling circuit: <= 690 V AC <= 400 Hz
[Ie] rated operational current9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit
[Uc] control circuit voltage24 V AC 50/60 Hz
Control circuit voltage limitsOperational: 0.8...1.15 Uc (at <50 °C) / Drop-out: >= 0.20 Uc (at <50 °C)
power pole contact composition3 NO
RangeTeSys
Device short nameLC1K
ParameterValue
Connections - terminalsSpring terminals 1 cable(s) 0.75…1.5 mm²solidSpring terminals 1 cable(s) 0.75…1.5 mm²flexible without cable endSpring terminals 2 cable(s) 0.75…1.5 mm²flexible without cable end
Height58 mm
Width45 mm
Depth57 mm
Ambient air temperature for storage-50…80 °C
Operating altitude2000 m without derating
Product certificationsCB SchemeCCCULCSAEACCEUKCA