Last Updated: 11/24/2026

Q1Can you supply the Schneider ATV6000C138A6666ND?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider ATV6000C138A6666ND cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
ATV6000C138A6666ND
Material Number
—
Manufacturer
Schneider
Product ID
38020

Get a Free Quote

Request pricing and availability for ATV6000C138A6666ND.

More parts to source? Send your whole list in one enquiry

Key specifications

[Us] rated supply voltage
6.6 kV +/- 10 %
Maximum Horse Power Rating
1408.0 hp heavy duty / 1475.0 hp normal duty
Communication Port Protocol
Ethernet IP/Modbus TCP
IP degree of protection
IP31 conforming to IEC 60529
See all specifications

Product Highlights

  1. Efficiency: 0.985 inverter efficiency and 0.96 total drive efficiency including transformer
  2. Power Rating: 1100 kW normal duty and 1050 kW heavy duty, with continuous output current of 115 A normal duty and 110 A heavy duty
  3. Temporary Current Boost: 1.2 x In for 60 s and 1.5 x In for 3 s normal duty, 1.5 x In for 60 s and 1.8 x In for 3 s heavy duty
  4. Supply: 6.6 kV +/- 10 % three-phase input at 50 Hz +/- 5 %, 30-pulse diode rectifier bridge, maximum THDI <3 % per IEEE 519-1992 and power factor 96
  5. Output: IGBT inverter cells with multilevel PWM, output voltage up to supply voltage, output frequency 0.1...120 Hz with 0.01 Hz resolution
  6. Cooling and Protection: Forced convection cooling with 12679.2 m3/h airflow, 83 dB noise level, and IP31 protection conforming to IEC 60529
  7. Motor Compatibility: Asynchronous, synchronous, and permanent magnet motors with closed loop vector, U/F vector, energy saving, open loop vector with slip compensation, and permanent magnet open/closed loop control profiles
  8. Enclosure: Floor-standing light grey RAL 7035 enclosure, 3660 mm wide x 1400 mm deep x 2617 mm high, 5045 kg net weight, bottom cable entry
  9. Interface: 10 inch LCD touch screen multi-language display, integrated IEC 61800-3 category C3 control and category C4 power EMC filters
  10. Communication and I/O: Ethernet IP/Modbus TCP, 2 RJ45 control block connectors, 1 RJ45 Modbus serial, 10 discrete inputs, 2 analog inputs, 2 analog outputs, 2 discrete outputs, and 3 relay outputs
  11. Protection Functions: Line supply overvoltage, undervoltage, phase loss, DC bus overvoltage, transformer thermal overload, cabinet overheating, overcurrent, overload, short-circuit, IGBT per cell, motor thermal protection, motor phase break, motor earth fault, control circuit break, and fan monitoring
  12. Standards and Markings: IEC 61800-3, EN/IEC 61800-4, IEC 61800-5-1, IEC 60529, IEEE 519:1992, EN/IEC 60076, UL 347A, CULus, CE, UKCA
ATV6000C138A6666ND

Product Information

Technical Specifications

Specifications for ATV6000C138A6666ND

ParameterValue
Product or Component TypeMedium voltage variable speed drive
Range of ProductAltivar Process ATV6000
[Us] rated supply voltage6.6 kV +/- 10 %
Maximum Horse Power Rating1408.0 hp heavy duty / 1475.0 hp normal duty
Apparent power1380 kVA
Power factor96
Motor power kW1100 kW normal duty / 1050 kW heavy duty
Communication Port ProtocolEthernet IP/Modbus TCP
Connector type2 RJ45 on the control block)Ethernet IP/Modbus TCP / 1 RJ45 on the control block)Modbus serial
ParameterValue
Height103.03 in (2617.0 mm)
Width144.09 in (3660.0 mm)
Depth55.1 in (1400.0 mm)
IP degree of protectionIP31 conforming to IEC 60529
Ambient air temperature for operation32…104 °F (0…40 °C)104…122 °F (40…50 °C) with derating factor-13…158 °F (-25…70 °C) during transport
StandardsIEC 61800-3EN/IEC 61800-4IEC 61800-5-1IEC 60529IEEE 519:1992EN/IEC 60076UL 347A