Industrial Automation Parts. Prompt replies from real people.

Schneider TSXAEY414 Analog Input Module

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider TSXAEY414?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider TSXAEY414 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
TSXAEY414
Material Number
—
Manufacturer
Schneider
Product ID
34864

Get a Free Quote

Request pricing and availability for TSXAEY414.

More parts to source? Send your whole list in one enquiry

Key specifications

Product or component type
Analog input module
Range of product
Modicon Premium Automation platform
Overcurrent
-30…30 mA at state 1 250 kOhm
Current consumption
660 mA at 5 V DC
Net weight
0.32 kg
IP degree of protection
IP20
See all specifications

Product Highlights

  1. Product Type: Modicon Premium analog input module with 4 low-level input channels
  2. Input Types: Current 4...20 mA, voltage ±10 V, 0...10 V, 0...5 V, 1...5 V, ±5 V, -13...63 mV, thermocouple types B, E, J, K, L, N, R, S, T, U, resistor 0...400 Ohm and 0...3850 Ohm, and 2-wire or 4-wire Ni 1000, Pt 100, and Pt 1000 temperature probes
  3. Conversion and Read Cycle: 16-bit analog-to-digital conversion with a nominal read cycle time of 550 ms
  4. Measurement Error: 0.13 % of full scale for 0...400 Ohm and 0.16 % for 0...10 V at 25 °C, rising to 0.86 % for 4...20 mA over 0...60 °C, with thermocouple errors from 1.5 °C to 12 °C depending on type and reference
  5. Isolation: 1780 Vrms between channels and bus or ground, 2830 Vrms between channels, 415 V AC or 200 V DC common mode between channels, and 240 V AC or 110 V DC common mode between channels and earth
  6. Operating Conditions and Protection: 0...60 °C operating temperature, 10...95 % relative humidity without condensation, 0...2000 m operating altitude, IP20 protection, pollution degree 2, and TC protective treatment
  7. Compliance and Connection: Screw terminal block connection, CE marking, and compliance with DIN 43760, IEC 584, IEC 751, DIN 43710, NFC 42-330, and IEC 1131
TSXAEY414

Product Information

Technical Specifications

Specifications for TSXAEY414
ParameterValue
Product or component typeAnalog input module
Range of productModicon Premium Automation platform
Overcurrent-30…30 mA at state 1 250 kOhm
Current consumption660 mA at 5 V DC
MarkingCE
Input levelLow level
Analogue input number4
Analogue input typeCurrent 4...20 mAVoltage +/- 10 VVoltage 0...10 VVoltage 0...5 VVoltage 1...5 VThermocouple thermocouple BThermocouple thermocouple EThermocouple thermocouple JThermocouple thermocouple KThermocouple thermocouple LThermocouple thermocouple NThermocouple thermocouple RThermocouple thermocouple SThermocouple thermocouple TThermocouple thermocouple UResistor 0...3850 OhmResistor 0...400 OhmTemperature probe Ni 1000 2 wiresTemperature probe Ni 1000 4 wiresTemperature probe Pt 100 2 wiresTemperature probe Pt 100 4 wiresTemperature probe Pt 1000 2 wiresTemperature probe Pt 1000 4 wiresVoltage - 13...63 mVVoltage +/- 5 V
Analog/digital conversion16 bits
Nominal read cycle time550 ms
Electrical connectionScrew terminal block
Net weight0.32 kg
IP degree of protectionIP20
Ambient air temperature for operation0…60 °C
Product certificationsDNVBVABSRMRSRINAGLLR

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.