Industrial Automation Parts. Prompt replies from real people.

Schneider RXM4GB3ED Relay

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the Schneider RXM4GB3ED?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider RXM4GB3ED cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
RXM4GB3ED
Material Number
—
Manufacturer
Schneider
Product ID
34230

Get a Free Quote

Request pricing and availability for RXM4GB3ED.

More parts to source? Send your whole list in one enquiry

Key specifications

Rated operational voltage limits
38.4...52.8 V DC
[Ie] rated operational current
2 A at 28 V (DC) NO conforming to IEC / 2 A at 250 V (AC) NO conforming to IEC / 1 A at 28 V (DC) NC conforming to IEC / 1 A at 250 V (AC) NC conforming to IEC / 3 A at 28 V (DC) conforming to UL / 3 A at 277 V (AC) conforming to UL
[Uc] control circuit voltage
48 V DC
Series name
Miniature
Net weight
0.037 kg
IP degree of protection
IP40 conforming to IEC 60529
See all specifications

Product Highlights

  1. Contacts: 4 C/O contacts made of gold plated bifurcated silver
  2. Control Circuit: 48 V DC control voltage with rated operational limits of 38.4 to 52.8 V DC and average coil consumption of 0.9 W
  3. Switching Capacity: Maximum switching voltage 250 V IEC, resistive rated load 3 A at 250 V AC and 3 A at 28 V DC, maximum switching capacity 750 VA/84 W, minimum switching capacity 15 mW at 3 mA and 5 V
  4. Durability: Mechanical durability 10000000 cycles and electrical durability 100000 cycles resistive depending on mounting position and working environment
  5. Operating Rate: Up to 1200 cycles/hour under load and up to 18000 cycles/hour no-load
  6. Insulation and Protection: Rated insulation voltage 250 V IEC, 300 V CSA, 300 V UL, rated impulse withstand voltage 2.5 kV 1.2/50 µs, dielectric strength 1300 V AC between contacts with micro disconnection, 2000 V AC between coil and contact, 2000 V AC between poles, IP40 conforming to IEC 60529
  7. Thermal Current and Temperature Range: Conventional enclosed thermal current 3 A at -40 to 55 °C (-40 to 131 °F)
  8. Coil Timing: Operate time 20 ms and release time 20 ms with drop-out voltage threshold >= 0.1 Uc
  9. Certifications and Standards: UL, Lloyd's, CEC, CSA, GOST, IECEE CB Scheme, UL 508, IEC 61810-1, CSA C22.2 No 14
RXM4GB3ED

Product Information

Technical Specifications

Specifications for RXM4GB3ED

ParameterValue
Product or component typePlug-in relay
Range of productHarmony Relay
Rated operational voltage limits38.4...52.8 V DC
[Ie] rated operational current2 A at 28 V (DC) NO conforming to IEC2 A at 250 V (AC) NO conforming to IEC1 A at 28 V (DC) NC conforming to IEC1 A at 250 V (AC) NC conforming to IEC3 A at 28 V (DC) conforming to UL3 A at 277 V (AC) conforming to UL
[Uc] control circuit voltage48 V DC
[Ithe] conventional enclosed thermal current3 A at -40…55 °C
ParameterValue
Load current3 A at 250 V AC / 3 A at 28 V DC
Series nameMiniature
Device short nameRXM
Net weight0.037 kg
Contacts materialGold plated bifurcated silver
Shape of pinFlat
IP degree of protectionIP40 conforming to IEC 60529
Ambient air temperature for operation-40…55 °C
Product certificationsULLloyd'sCECSAGOSTIECEE CB Scheme

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp
RXM4GB3ED Relay by Schneider Electric - High-Quality Electrical Solutions