Industrial Automation Parts. Prompt replies from real people.

Schneider RM4UA31MW Voltage Measurement Relay

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the Schneider RM4UA31MW?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider RM4UA31MW cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
RM4UA31MW
Material Number
—
Manufacturer
Schneider
Product ID
33730

Get a Free Quote

Request pricing and availability for RM4UA31MW.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ie] rated operational current
2 A at 70 °C 24 V DC-13 conforming to IEC 60947-5-1/1991 / 2 A at 70 °C 24 V DC-13 conforming to VDE 0660 / 3 A at 70 °C 115 V AC-15 conforming to IEC 60947-5-1/1991 / 3 A at 70 °C 115 V AC-15 conforming to VDE 0660 / 3 A at 70 °C 24 V AC-15 conforming to IEC 60947-5-1/1991 / 3 A at 70 °C 24 V AC-15 conforming to VDE 0660 / 3 A at 70 °C 250 V AC-15 conforming to IEC 60947-5-1/1991 / 3 A at 70 °C 250 V AC-15 conforming to VDE 0660 / 0.1 A at 70 °C 250 V DC-13 conforming to IEC 60947-5-1/1991 / 0.1 A at 70 °C 250 V DC-13 conforming to VDE 0660 / 0.3 A at 70 °C 115 V DC-13 conforming to IEC 60947-5-1/1991 / 0.3 A at 70 °C 115 V DC-13 conforming to VDE 0660
Power consumption in VA
1.5…3.3 VA AC
Net weight
0.08 kg
Contacts material
90/10 silver nickel contacts
IP degree of protection
IP20 (terminals) conforming to IEC 60529 / IP50 (casing) conforming to IEC 60529
See all specifications

Product Highlights

  1. Voltage Monitoring: Detects overvoltage or undervoltage with an adjustable switching threshold hysteresis of 5 to 30 percent and threshold setting accuracy of plus or minus 5 percent
  2. Adjustable Time Delay: Time delay adjustable from 0.05 to 30 seconds with 10 percent setting accuracy
  3. Output Contacts: Two changeover (2 C/O) contacts rated 8 A conventional thermal current and 2 to 3 A operational current at 70 °C depending on voltage and utilization category
  4. Supply Voltage Tolerance: Operates within 0.85 to 1.1 Uc with supply disconnection value above 0.1 Uc
  5. Terminal Connections: Screw terminals accept 2 x 1.5 mm² flexible conductors with cable ends or 2 x 2.5 mm² flexible conductors without cable ends, tightened to 0.6 to 1.1 N·m
RM4UA31MW

Product Information

Technical Specifications

Specifications for RM4UA31MW
ParameterValue
Product or component typeIndustrial measurement and control relays
Range of productHarmony Relay
[Ie] rated operational current2 A at 70 °C 24 V DC-13 conforming to IEC 60947-5-1/19912 A at 70 °C 24 V DC-13 conforming to VDE 06603 A at 70 °C 115 V AC-15 conforming to IEC 60947-5-1/19913 A at 70 °C 115 V AC-15 conforming to VDE 06603 A at 70 °C 24 V AC-15 conforming to IEC 60947-5-1/19913 A at 70 °C 24 V AC-15 conforming to VDE 06603 A at 70 °C 250 V AC-15 conforming to IEC 60947-5-1/19913 A at 70 °C 250 V AC-15 conforming to VDE 06600.1 A at 70 °C 250 V DC-13 conforming to IEC 60947-5-1/19910.1 A at 70 °C 250 V DC-13 conforming to VDE 06600.3 A at 70 °C 115 V DC-13 conforming to IEC 60947-5-1/19910.3 A at 70 °C 115 V DC-13 conforming to VDE 0660
Power consumption in VA1.5…3.3 VA AC
Maximum power consumption in W1.2 W DC
[Ith] conventional free air thermal current8 A
Operating positionAny position without derating
Supply disconnection value> 0.1 Uc
Connections - terminalsScrew terminals, 2 x 1.5 mm²flexible with cable end / Screw terminals, 2 x 2.5 mm²flexible without cable end
Width22.5 mm
Net weight0.08 kg
Contacts material90/10 silver nickel contacts
IP degree of protectionIP20 (terminals) conforming to IEC 60529 / IP50 (casing) conforming to IEC 60529
Ambient air temperature for operation-20…65 °C
Product certificationsGLULCSA

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.