Industrial Automation Parts. Prompt replies from real people.

Schneider RM4TU02 Interface and Control Relays

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the Schneider RM4TU02?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider RM4TU02 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
RM4TU02
Material Number
—
Manufacturer
Schneider
Product ID
33717

Get a Free Quote

Request pricing and availability for RM4TU02.

More parts to source? Send your whole list in one enquiry

Key specifications

Product or component type
Industrial measurement and control relays
Range of product
Harmony Relay
[Ie] rated operational current
2 A at 70 °C 24 V DC-13 conforming to IEC 60947-5-1/1991 / 2 A at 70 °C 24 V DC-13 conforming to VDE 0660 / 3 A at 70 °C 115 V AC-15 conforming to IEC 60947-5-1/1991 / 3 A at 70 °C 115 V AC-15 conforming to VDE 0660 / 3 A at 70 °C 24 V AC-15 conforming to IEC 60947-5-1/1991 / 3 A at 70 °C 24 V AC-15 conforming to VDE 0660 / 3 A at 70 °C 250 V AC-15 conforming to IEC 60947-5-1/1991 / 3 A at 70 °C 250 V AC-15 conforming to VDE 0660 / 0.1 A at 70 °C 250 V DC-13 conforming to IEC 60947-5-1/1991 / 0.1 A at 70 °C 250 V DC-13 conforming to VDE 0660 / 0.3 A at 70 °C 115 V DC-13 conforming to IEC 60947-5-1/1991 / 0.3 A at 70 °C 115 V DC-13 conforming to VDE 0660
[Ith] conventional free air thermal current
8 A
Poles description
3P
IP degree of protection
IP20 (terminals) conforming to IEC 60529 / IP50 (casing) conforming to IEC 60529
See all specifications

Product Highlights

  1. Three-Phase Monitoring: Monitors phase sequence, undervoltage, and phase failure in 3-phase supplies
  2. Output Contacts: Two C/O contacts rated 8 A conventional thermal current and up to 440 V AC maximum switching voltage
  3. Undervoltage Threshold: Adjustable 300 to 430 V with +/-3 % setting accuracy and 5 % fixed de-energisation hysteresis
  4. Supply and Response: 50/60 Hz +/- 5 % supply frequency, 650 ms power-up delay, and 80 ms maximum measuring cycle
  5. Mechanical Durability: 30 million operating cycles with 90/10 silver nickel contacts
  6. Mounting and Environment: Any-position mounting without derating, -20 to 65 °C operating temperature, and IP20 terminals / IP50 casing
  7. Compliance: EN/IEC 60255-6 standard with CSA, GL, UL certifications and CE marking
RM4TU02

Product Information

Technical Specifications

Specifications for RM4TU02
ParameterValue
Product or component typeIndustrial measurement and control relays
Range of productHarmony Relay
[Ie] rated operational current2 A at 70 °C 24 V DC-13 conforming to IEC 60947-5-1/19912 A at 70 °C 24 V DC-13 conforming to VDE 06603 A at 70 °C 115 V AC-15 conforming to IEC 60947-5-1/19913 A at 70 °C 115 V AC-15 conforming to VDE 06603 A at 70 °C 24 V AC-15 conforming to IEC 60947-5-1/19913 A at 70 °C 24 V AC-15 conforming to VDE 06603 A at 70 °C 250 V AC-15 conforming to IEC 60947-5-1/19913 A at 70 °C 250 V AC-15 conforming to VDE 06600.1 A at 70 °C 250 V DC-13 conforming to IEC 60947-5-1/19910.1 A at 70 °C 250 V DC-13 conforming to VDE 06600.3 A at 70 °C 115 V DC-13 conforming to IEC 60947-5-1/19910.3 A at 70 °C 115 V DC-13 conforming to VDE 0660
[Ith] conventional free air thermal current8 A
Poles description3P
MarkingCE
Operating positionAny position without derating
Relay typeControl relay
Connections - terminalsScrew terminals, 2 x 1.5 mm²flexible with cable end / Screw terminals, 2 x 2.5 mm²flexible without cable end
Height78 mm
Width22.5 mm
Depth80 mm
IP degree of protectionIP20 (terminals) conforming to IEC 60529 / IP50 (casing) conforming to IEC 60529
Ambient air temperature for operation-20…65 °C
Product certificationsCSAGLUL

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp