Industrial Automation Parts. Prompt replies from real people.

Schneider RM4JA32M Current Measurement Relay

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the Schneider RM4JA32M?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider RM4JA32M cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
RM4JA32M
Material Number
—
Manufacturer
Schneider
Product ID
33703

Get a Free Quote

Request pricing and availability for RM4JA32M.

More parts to source? Send your whole list in one enquiry

Key specifications

Product or component type
Industrial measurement and control relays
Range of product
Harmony Relay
[Ie] rated operational current
2 A at 24 V DC-13 conforming to IEC 60947-5-1/1991 70 °C / 2 A at 24 V DC-13 conforming to VDE 0660 70 °C / 3 A at 115 V AC-15 conforming to IEC 60947-5-1/1991 70 °C / 3 A at 115 V AC-15 conforming to VDE 0660 70 °C / 3 A at 24 V AC-15 conforming to IEC 60947-5-1/1991 70 °C / 3 A at 24 V AC-15 conforming to VDE 0660 70 °C / 3 A at 250 V AC-15 conforming to IEC 60947-5-1/1991 70 °C / 3 A at 250 V AC-15 conforming to VDE 0660 70 °C / 0.1 A at 250 V DC-13 conforming to IEC 60947-5-1/1991 70 °C / 0.1 A at 250 V DC-13 conforming to VDE 0660 70 °C / 0.3 A at 115 V DC-13 conforming to IEC 60947-5-1/1991 70 °C / 0.3 A at 115 V DC-13 conforming to VDE 0660 70 °C
Maximum power consumption in VA
3.4 VA AC
[Ith] conventional free air thermal current
8 A
IP degree of protection
IP20 (terminals) conforming to IEC 60529 / IP50 (casing) conforming to IEC 60529
See all specifications

Product Highlights

  1. Current Monitoring: Overcurrent or undercurrent detection with measurement ranges of 1...5 A AC/DC, 3...15 A AC/DC, and 300...1500 mA AC/DC
  2. Time Delay: Adjustable 0.05...30 s with setting accuracy of 10 P and drift of <= 0.07 % per degree centigrade
  3. Output Contacts: 2 C/O contacts with 90/10 silver nickel contact material, maximum switching voltage 440 V AC, and switching capacity of 10 mA at 12 V
  4. Overload Capability: Permissible continuous overload of 7 A, 20 A, or 2 A and non-repetitive overload of 10 A for <= 3 s, 100 A, or 15 A
  5. Threshold Accuracy: Switching threshold setting accuracy of +/-5 % with drift <= 0.06 % per degree centigrade and <= 0.5 % within the 0.85...1.1 Un supply voltage range
  6. Hysteresis: Adjustable 5...30 % of current threshold setting
  7. Operating Voltage Tolerance: 0.85...1.1 Uc
  8. Maximum Measuring Cycle: 80 ms
  9. Internal Input Resistance: 0.02 Ohm, 0.06 Ohm, or 0.006 Ohm
  10. Maximum Power Consumption: 3.4 VA AC
  11. Mechanical Durability: 30,000,000 cycles
  12. Operating Position: Any position without derating
  13. Terminal Connections: Screw terminals for 2 x 1.5 mm2 flexible with cable end or 2 x 2.5 mm2 flexible without cable end, tightening torque 0.6...1.1 N.m
  14. Ambient Air Temperature: -20...65 degC for operation and -40...85 degC for storage
  15. Protection: IP20 terminals and IP50 casing, pollution degree 3, overvoltage category III
  16. Compliance: EN/IEC 60255-6, UL, GL, CSA, CE LVD 73/23/EEC and EMC 89/336/EEC
RM4JA32M

Product Information

Technical Specifications

Specifications for RM4JA32M
ParameterValue
Product or component typeIndustrial measurement and control relays
Range of productHarmony Relay
[Ie] rated operational current2 A at 24 V DC-13 conforming to IEC 60947-5-1/1991 70 °C2 A at 24 V DC-13 conforming to VDE 0660 70 °C3 A at 115 V AC-15 conforming to IEC 60947-5-1/1991 70 °C3 A at 115 V AC-15 conforming to VDE 0660 70 °C3 A at 24 V AC-15 conforming to IEC 60947-5-1/1991 70 °C3 A at 24 V AC-15 conforming to VDE 0660 70 °C3 A at 250 V AC-15 conforming to IEC 60947-5-1/1991 70 °C3 A at 250 V AC-15 conforming to VDE 0660 70 °C0.1 A at 250 V DC-13 conforming to IEC 60947-5-1/1991 70 °C0.1 A at 250 V DC-13 conforming to VDE 0660 70 °C0.3 A at 115 V DC-13 conforming to IEC 60947-5-1/1991 70 °C0.3 A at 115 V DC-13 conforming to VDE 0660 70 °C
Maximum power consumption in VA3.4 VA AC
[Ith] conventional free air thermal current8 A
MarkingCE : LVD 73/23/EEC / CE : EMC 89/336/EEC
Operating positionAny position without derating
Supply disconnection value> 0.1 Uc
Connections - terminalsScrew terminals, 2 x 1.5 mm²flexible with cable end / Screw terminals, 2 x 2.5 mm²flexible without cable end
Height78 mm
Width45 mm
Depth80 mm
IP degree of protectionIP20 (terminals) conforming to IEC 60529 / IP50 (casing) conforming to IEC 60529
Ambient air temperature for operation-20…65 °C
Product certificationsULGLCSA

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.