Industrial Automation Parts. Prompt replies from real people.

Schneider LC2K1201B72 Reversing Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the Schneider LC2K1201B72?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC2K1201B72 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC2K1201B72
Material Number
—
Manufacturer
Schneider
Product ID
33558

Get a Free Quote

Request pricing and availability for LC2K1201B72.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: 690 V AC 50/60 Hz / Signalling circuit: <= 690 V AC 50/60 Hz
[Ie] rated operational current
20 A (at <50 °C) at <= 440 V AC AC-1 for power circuit / 16 A (at <70 °C) at 690 V AC AC-1 for power circuit / 12 A at <= 440 V AC AC-3 for power circuit / 12 A at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage
24 V AC 50/60 Hz
IP degree of protection
IP20 conforming to VDE 0106
See all specifications

Product Highlights

  1. Product Type: TeSys K reversing contactor, device short name LC2K, preassembled with reversing power busbar
  2. Configuration: 3 poles, 3 NO power pole contacts, mechanical interlocking, 1 NC instantaneous auxiliary contact
  3. Rated Operational Current: 12 A at up to 440 V AC in AC-3 and AC-3e, 20 A at up to 440 V AC in AC-1 at 50 °C, 16 A at 690 V AC in AC-1 at 70 °C
  4. Motor Power: 3 kW at 220...230 V AC, 5.5 kW at 380...415 V AC and 440 V AC, 4 kW at 480 V AC, 500...600 V AC and 660...690 V AC, 50/60 Hz
  5. Control Circuit: AC 50/60 Hz with 24 V AC coil, built-in bidirectional peak limiting diode suppressor, 30 VA inrush and 4.5 VA hold-in at 20 °C
  6. Rated Operational Voltage: Power circuit 690 V AC 50/60 Hz, signalling circuit up to 690 V AC 50/60 Hz, rated impulse withstand voltage 8 kV, overvoltage category III
  7. Electrical Durability: 1.3 million cycles at 12 A AC-3 or AC-3e up to 440 V, 0.3 million cycles at 20 A AC-1 up to 690 V, 0.02 million cycles at 72 A AC-4 up to 440 V
  8. Mechanical Durability: 5 million cycles, maximum operating rate 3600 cycles per hour, operating time 10...20 ms for coil energisation and NO closing or de-energisation and NO opening
  9. Connections: Screw clamp terminals for 0.34...4 mm² conductors, tightening torque 0.8...1.3 N·m
  10. Environment: IP20 protection, ambient operating temperature -25...50 °C, storage temperature -50...80 °C, operating altitude up to 2000 m without derating
  11. Standards and Certifications: EN/IEC 60947-4-1, GB/T 14048.4, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, CB Scheme, CCC, UL, CSA, EAC, CE, UKCA
LC2K1201B72

Product Information

Technical Specifications

Specifications for LC2K1201B72

ParameterValue
Product or component typeReversing contactor
[Ue] rated operational voltagePower circuit: 690 V AC 50/60 Hz / Signalling circuit: <= 690 V AC 50/60 Hz
[Ie] rated operational current20 A (at <50 °C) at <= 440 V AC AC-1 for power circuit16 A (at <70 °C) at 690 V AC AC-1 for power circuit12 A at <= 440 V AC AC-3 for power circuit12 A at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage24 V AC 50/60 Hz
Control circuit voltage limitsOperational: 0.8...1.15 Uc (at <50 °C) / Drop-out: 0.2...0.75 Uc (at <50 °C)
power pole contact composition3 NO
RangeTeSys
Product nameTeSys K
ParameterValue
Connections - terminalsScrew clamp terminals 1 cable(s) 1.5…4 mm²solidScrew clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable endScrew clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable endScrew clamp terminals 2 cable(s) 1.5…4 mm²solidScrew clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable endScrew clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end
Height58 mm
Width90 mm
Depth57 mm
IP degree of protectionIP20 conforming to VDE 0106
Ambient air temperature for operation-25…50 °C
Product certificationsCB SchemeCCCULCSAEACCEUKCA

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp