Q1Can you supply the Schneider LC1G1854LSEA?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1G1854LSEA cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1G1854LSEA
Material Number
—
Manufacturer
Schneider
Product ID
33482

Get a Free Quote

Request pricing and availability for LC1G1854LSEA.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current
185 A (at <60 °C) at <= 440 V AC-3 / 305 A (at <40 °C) at <= 1000 V AC-1
[Uc] control circuit voltage
200...500 V AC 50/60 Hz / 200...500 V DC
IP degree of protection
IP2X front face with shrouds conforming to IEC 60529 / IP2X front face with shrouds conforming to VDE 0106
See all specifications

Product Highlights

  1. Pole Configuration: 4 NO power poles with 1 NO + 1 NC auxiliary contacts
  2. Coil Technology: Built-in bidirectional peak limiting, 215 W inrush power (DC), 8.0 W hold-in power (DC)
  3. Rated Operational Voltage: <= 1000 V AC 50/60 Hz, <= 460 V DC
  4. Rated Operational Current: 185 A at <= 440 V AC-3 (at <= 60 °C), 305 A at <= 1000 V AC-1 (at <= 40 °C)
  5. Rated Breaking Capacity: 1610 A at 440 V, with 2310 A rms rated making capacity at 440 V
  6. Rated Short-Time Withstand Current: 1.5 kA for 10 s, 0.92 kA for 30 s, 0.74 kA for 1 min, 0.5 kA for 3 min, 0.4 kA for 10 min
  7. Associated Fuse Rating: 200 A aM at <= 440 V for motor, 160 A aM at <= 690 V for motor, 315 A gG at <= 690 V
  8. Rated Impulse Withstand Voltage: 8 kV, overvoltage category III, rated insulation voltage 1000 V
  9. Mechanical Durability: 8 Mcycles, B10d = 400000 cycles with nominal load and 3000000 cycles with mechanical load per EN/ISO 13849-1
  10. Operating Time: 40...70 ms closing, 15...50 ms opening, maximum operating rate 600 cyc/h AC-3, 300 cyc/h AC-1
  11. Connections: Power circuit bar 25 x 6 mm or lugs-ring terminals 185 mm², control circuit push-in 0.2...2.5 mm², tightening torque 18 N.m
  12. Ambient Air Temperature for Operation: -25...60 °C, storage -60...80 °C, permissible around device -40...70 °C at Uc
LC1G1854LSEA

Product Information

Technical Specifications

Specifications for LC1G1854LSEA

ParameterValue
Product or component typeContactor
Range of productTeSys Giga
[Ue] rated operational voltage<= 1000 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current185 A (at <60 °C) at <= 440 V AC-3 / 305 A (at <40 °C) at <= 1000 V AC-1
[Uc] control circuit voltage200...500 V AC 50/60 Hz / 200...500 V DC
Control circuit voltage limitsOperational: 0.8 Uc Min...1.1 Uc Max (at <60 °C) / Drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)
Power dissipation per pole20 W AC-1 - Ith 305 A / 6 W AC-3 - Ith 185 A
Connections - terminalsPower circuit: bar 2 - busbar cross section: 25 x 6 mmPower circuit: lugs-ring terminals 1 185 mm²Power circuit: bolted connectionControl circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable endControl circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable endControl circuit: push-in 2 0.5…1.0 mm² with cable endControl circuit: push-in 0.75…2.5 mm² - cable stiffness: solid stranded without cable endControl circuit: push-in 0.75…2.5 mm² - cable stiffness: flexible with cable end
ParameterValue
Connection pitch35 mm
Height255 mm
Width143 mm
Depth193 mm
IP degree of protectionIP2X front face with shrouds conforming to IEC 60529 / IP2X front face with shrouds conforming to VDE 0106
Ambient air temperature for operation-25…60 °C
Product certificationsCB SchemeCCCcULusEACCEUKCAEU-RO-MR by DNV-GL

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.