Q1Can you supply the Schneider LC1F800FW?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1F800FW cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1F800FW
Material Number
—
Manufacturer
Schneider
Product ID
33452

Get a Free Quote

Request pricing and availability for LC1F800FW.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current
1000 A (at <40 °C) at <= 440 V AC AC-1 / 800 A (at <55 °C) at <= 440 V AC AC-3
[Uc] control circuit voltage
110...125 V DC / 100...120 V AC 40...400 Hz
IP degree of protection
IP20 front face with shrouds conforming to IEC 60529 / IP20 front face with shrouds conforming to VDE 0106
See all specifications

Product Highlights

  1. Contactor Type: 3-pole contactor with 3 NO power poles for resistive load and motor control
  2. Utilisation Category: AC-1, AC-3 and AC-4 rated
  3. Rated Operational Voltage: Up to 1000 V AC 50/60 Hz and up to 460 V DC
  4. Rated Operational Current: 1000 A at 40 °C in AC-1 and 800 A at 55 °C in AC-3, both at up to 440 V AC
  5. Motor Power: 250 to 500 kW at 200 to 500 V AC 3-phase, including 450 kW at 380 to 440 V AC in AC-3
  6. Control Circuit: 110 to 125 V DC or 100 to 120 V AC 40 to 400 Hz, with screw clamp terminals for 1 to 4 mm² conductors
  7. Short-Circuit Protection: 6400 A rated breaking capacity per IEC 60947-4-1, 5500 A short-time withstand current for 10 s, and 1000 A gG or 800 A aM fuse at up to 440 V
  8. Compliance: IEC 60947-1, IEC 60947-4-1, EN 60947-1, EN 60947-4-1 and JIS C8201-4-1, with ABS, RMRS, RoS, CCC, UL, CB, CSA and UKCA certifications
LC1F800FW

Product Information

Technical Specifications

Specifications for LC1F800FW

ParameterValue
Product or component typeContactor
Range of productTeSys F
[Ue] rated operational voltage<= 1000 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current1000 A (at <40 °C) at <= 440 V AC AC-1 / 800 A (at <55 °C) at <= 440 V AC AC-3
[Uc] control circuit voltage110...125 V DC / 100...120 V AC 40...400 Hz
Control circuit voltage limitsOperational: 0.85...1.1 Uc (at 55 °C) / Drop-out: 0.3...0.5 Uc (at 55 °C)
Power dissipation per pole120 W AC-1 / 77 W AC-3
RangeTeSys
ParameterValue
Connections - terminalsControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable endControl circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable endControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable endControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable endControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable endControl circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable endPower circuit: bar 2 cable(s) - busbar cross section: 60 x 5 mmPower circuit: bolted connection
Height304 mm
Width309 mm
Depth255 mm
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 / IP20 front face with shrouds conforming to VDE 0106
Ambient air temperature for operation-5…55 °C
Product certificationsABSRMRoSCCCULCBCSAUKCA