| Range | TeSys |
|---|
| Range of Product | TeSys F |
|---|
| Product or Component Type | Contactor |
|---|
| Device short name | LC1F |
|---|
| Contactor application | Resistive loadMotor control |
|---|
| Utilisation category | AC-1AC-4AC-3 |
|---|
| Poles description | 3P |
|---|
| [Ue] rated operational voltage | <= 1000 V AC 50/60 Hz<= 460 V DC |
|---|
| [Uc] control circuit voltage | 415 V AC 40...400 Hz |
|---|
| [Ie] rated operational current | 400 A (at <104 °F (40 °C)) at <= 440 V AC AC-1330 A (at <131 °F (55 °C)) at <= 440 V AC AC-3 |
|---|
| [Uimp] rated impulse withstand voltage | 8 kV |
|---|
| [Ith] conventional free air thermal current | 400 A (at 104 °F (40 °C)) |
|---|
| Rated breaking capacity | 2640 A conforming to IEC 60947-4-1 |
|---|
| [Icw] rated short-time withstand current | 2650 A 104 °F (40 °C) - 10 s1800 A 104 °F (40 °C) - 30 s1300 A 104 °F (40 °C) - 1 min900 A 104 °F (40 °C) - 3 min750 A 104 °F (40 °C) - 10 min |
|---|
| Associated fuse rating | 400 A aM at <= 440 V500 A gG at <= 440 V |
|---|
| Average impedance | 0.28 mOhm - Ith 400 A 50 Hz |
|---|
| [Ui] rated insulation voltage | 1000 V IEC 60947-4-1 1500 V VDE 0110 group C |
|---|
| Power dissipation per pole | 44 W AC-131 W AC-3 |
|---|
| Overvoltage category | III |
|---|
| power pole contact composition | 3 NO |
|---|
| Motor power kW | 160 kW at 380...400 V AC 50/60 Hz (AC-3)180 kW at 415 V AC 50/60 Hz (AC-3)200 kW at 440 V AC 50/60 Hz (AC-3)200 kW at 500 V AC 50/60 Hz (AC-3)220 kW at 660...690 V AC 50/60 Hz (AC-3)160 kW at 1000 V AC 50/60 Hz (AC-3)100 kW at 220...230 V AC 50/60 Hz (AC-3)59 kW at 400 V AC 50/60 Hz (AC-4) |
|---|
| Control circuit voltage limits | Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C))Drop-out 0.35...0.55 Uc 40...400 Hz 131 °F (55 °C)) |
|---|
| Mechanical durability | 10 Mcycles |
|---|
| Inrush power in VA | 650 VA, 40...400 Hz 0.9 68 °F (20 °C)) |
|---|