Product Model
LC1F265F722L
Material Number
—
Manufacturer
Schneider
Product ID
33296

Get a Free Quote

Request pricing and availability for LC1F265F722L.

More parts to source? Send your whole list in one enquiry

Key specifications

Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz <= 460 V DC
[Uc] control circuit voltage
110 V AC 40...400 Hz
[Ie] rated operational current
350 A (at <104 °F (40 °C)) at <= 440 V AC AC-1265 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
Hold-in power consumption in VA
10 VA 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))
IP degree of protection
IP20 front face with shrouds IEC 60529IP20 front face with shrouds VDE 0106
See all specifications

Product Highlights

  1. Contactor Type: TeSys F 3-pole contactor with 3 NO power poles and 2 NO + 2 NC auxiliary contacts
  2. Rated Operational Current: 350 A at 40 °C and 265 A at 55 °C for AC-3 at up to 440 V AC
  3. Motor Power Ratings: 132 kW at 380–400 V AC, 140 kW at 415–440 V AC, 160 kW at 500–690 V AC, and 147 kW at 1000 V AC in AC-3
  4. Coil and Control: 110 V AC control circuit at 40–400 Hz with operational range 0.85–1.1 Uc and drop-out 0.15–0.2 Uc
  5. Short-Circuit Protection: 315 A aM or 400 A gG fuse at up to 440 V AC and 2200 A short-time withstand current for 10 s at 40 °C
  6. Terminations and Mounting: Screw clamp control terminals, bolted power connections for 32 x 4 mm bars or 240 mm² lugs, and plate mounting
  7. Operating Temperature: -5 to 55 °C ambient for operation and -60 to 80 °C for storage
LC1F265F722L

Product Information

Technical Specifications

Specifications for LC1F265F722L

ParameterValue
Range of ProductTeSys F
Product or Component TypeContactor
Device short nameLC1F
Contactor applicationResistive loadMotor control
Utilisation categoryAC-3AC-4AC-1
Poles description3P
[Ue] rated operational voltage<= 1000 V AC 50/60 Hz <= 460 V DC
[Uc] control circuit voltage110 V AC 40...400 Hz
[Ie] rated operational current350 A (at <104 °F (40 °C)) at <= 440 V AC AC-1265 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
[Uimp] rated impulse withstand voltage8 kV
[Ith] conventional free air thermal current350 A (at 104 °F (40 °C))
Rated breaking capacity2120 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current2200 A 104 °F (40 °C) - 10 s1230 A 104 °F (40 °C) - 30 s950 A 104 °F (40 °C) - 1 min620 A 104 °F (40 °C) - 3 min480 A 104 °F (40 °C) - 10 min
Associated fuse rating315 A aM at <= 440 V400 A gG at <= 440 V
Average impedance0.3 mOhm - Ith 350 A 50 Hz
[Ui] rated insulation voltage1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Power dissipation per pole37 W AC-121 W AC-3
Overvoltage categoryIII
power pole contact composition3 NO
Auxiliary contact composition2 NO + 2 NC
Motor power kW132 kW at 380...400 V AC 50/60 Hz (AC-3)140 kW at 415 V AC 50/60 Hz (AC-3)140 kW at 440 V AC 50/60 Hz (AC-3)160 kW at 500 V AC 50/60 Hz (AC-3)160 kW at 660...690 V AC 50/60 Hz (AC-3)147 kW at 1000 V AC 50/60 Hz (AC-3)75 kW at 220...230 V AC 50/60 Hz (AC-3)51 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)60 hp at 200 V AC75 hp at 230 V AC150 hp at 460 V AC200 hp at 575 V AC
Control circuit voltage limitsOperational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C))Drop-out 0.15...0.2 Uc 40...400 Hz 131 °F (55 °C))
Mechanical durability10 Mcycles
ParameterValue
Inrush power in VA650 VA, 40...400 Hz 0.9 68 °F (20 °C))
Maximum operating rate2400 cyc/h 131 °F (55 °C)
Operating time40...65 ms closing100...170 ms opening
Connections - terminalsControl circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable endControl circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable endControl circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable endControl circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable endControl circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable endControl circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable endPower circuit bolted connectionPower circuit 2 bars 32 x 4 mmPower circuit lugs-ring terminals 1 0.4 in² (240 mm²)Power circuit connector 1 0.4 in² (240 mm²)
Tightening torqueControl circuit 10.6 lbf.in (1.2 N.m)Power circuit 309.8 lbf.in (35 N.m)
Mounting SupportPlate
Heat dissipation8 W
StandardsIEC 60947-4-1JIS C8201-4-1EN 60947-1EN 60947-4-1IEC 60947-1
Product CertificationsBVRINAULDNVCSACBRMRoSABSLROS (Lloyds register of shipping)
Hold-in power consumption in VA10 VA 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))
IP degree of protectionIP20 front face with shrouds IEC 60529IP20 front face with shrouds VDE 0106
Protective treatmentTH
Ambient Air Temperature for Operation23...131 °F (-5...55 °C)
Ambient Air Temperature for Storage-76...176 °F (-60...80 °C)
Permissible ambient air temperature around the device-40...158 °F (-40...70 °C)
Mechanical robustnessVibrations contactor open2 Gn, 5...300 HzShocks contactor closed15 Gn for 11 msVibrations contactor closed5 Gn, 5...300 HzShocks contactor open6 Gn for 11 ms
Height14.8 in (375 mm)
Width7.9 in (201.5 mm)
Depth8.4 in (213 mm)
Operating altitude9842.52 ft (3000 m) without derating