| Range of Product | TeSys F |
|---|
| Product or Component Type | Contactor |
|---|
| Device short name | LC1F |
|---|
| Contactor application | Resistive loadMotor control |
|---|
| Utilisation category | AC-1AC-4AC-3 |
|---|
| Poles description | 3P |
|---|
| [Ue] rated operational voltage | <= 1000 V AC 50/60 Hz <= 460 V DC |
|---|
| [Uc] control circuit voltage | 110 V AC 40...400 Hz |
|---|
| [Ie] rated operational current | 700 A (at <104 °F (40 °C)) at <= 440 V AC AC-1500 A (at <131 °F (55 °C)) at <= 440 V AC AC-3 |
|---|
| [Uimp] rated impulse withstand voltage | 8 kV |
|---|
| [Ith] conventional free air thermal current | 700 A (at 104 °F (40 °C)) |
|---|
| Rated breaking capacity | 4000 A conforming to IEC 60947-4-1 |
|---|
| [Icw] rated short-time withstand current | 4200 A 104 °F (40 °C) - 10 s3200 A 104 °F (40 °C) - 30 s2400 A 104 °F (40 °C) - 1 min1500 A 104 °F (40 °C) - 3 min1200 A 104 °F (40 °C) - 10 min |
|---|
| Associated fuse rating | 500 A aM at <= 440 V800 A gG at <= 440 V |
|---|
| Average impedance | 0.18 mOhm - Ith 700 A 50 Hz |
|---|
| [Ui] rated insulation voltage | 1000 V IEC 60947-4-1 1500 V VDE 0110 group C |
|---|
| Overvoltage category | III |
|---|
| power pole contact composition | 3 NO |
|---|
| Auxiliary contact composition | 2 NO + 2 NC |
|---|
| Motor power kW | 250 kW at 380...400 V AC 50/60 Hz (AC-3)280 kW at 415 V AC 50/60 Hz (AC-3)295 kW at 440 V AC 50/60 Hz (AC-3)355 kW at 500 V AC 50/60 Hz (AC-3)335 kW at 660...690 V AC 50/60 Hz (AC-3)335 kW at 1000 V AC 50/60 Hz (AC-3)147 kW at 220...230 V AC 50/60 Hz (AC-3)80 kW at 400 V AC 50/60 Hz (AC-4) |
|---|
| motor power HP (UL / CSA) | 150 hp at 200 V AC200 hp at 230 V AC400 hp at 460 V AC500 hp at 575 V AC |
|---|
| Control circuit voltage limits | Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C))Drop-out 0.3...0.5 Uc 40...400 Hz 131 °F (55 °C)) |
|---|