| Maximum operating rate | 2400 cyc/h 131 °F (55 °C) |
|---|
| Connections - terminals | Power circuit 2 bars 20 x 3 mmPower circuit lugs-ring terminals 1 0.1 in² (95 mm²)Power circuit connector 1 0.1 in² (95 mm²)Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable endControl circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable endControl circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable endControl circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable endControl circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable endControl circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable endPower circuit bolted connection |
|---|
| Tightening torque | Power circuit 88.5 lbf.in (10 N.m)Control circuit 10.6 lbf.in (1.2 N.m) |
|---|
| Mounting Support | Plate |
|---|
| Heat dissipation | 12...16 W |
|---|
| Standards | IEC 60947-4-1EN 60947-4-1EN 60947-1JIS C8201-4-1IEC 60947-1 |
|---|
| Product Certifications | DNVCBRINALROS (Lloyds register of shipping)ABSCCCULBVRMRoS |
|---|
| Hold-in power consumption in VA | 55 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C)) |
|---|
| IP degree of protection | IP2X front face with shrouds IEC 60529IP2X front face with shrouds VDE 0106 |
|---|
| Protective treatment | TH |
|---|
| Ambient Air Temperature for Operation | -40...140 °F (-40...60 °C) |
|---|
| Ambient Air Temperature for Storage | -76...176 °F (-60...80 °C) |
|---|
| Permissible ambient air temperature around the device | 140...158 °F (60...70 °C) at Uc |
|---|
| Mechanical robustness | Vibrations contactor open2 Gn, 5...300 HzVibrations contactor closed6 Gn, 5...300 HzShocks contactor open9 Gn for 11 msShocks contactor closed15 Gn for 11 ms |
|---|
| Height | 10.4 in (265 mm) |
|---|
| Width | 6.4 in (163.3 mm) |
|---|
| Depth | 6.7 in (171 mm) |
|---|
| Operating altitude | 9842.52 ft (3000 m) without derating |
|---|