Industrial Automation Parts. Prompt replies from real people.

Schneider LC1DT40G7 Non-Reversing Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider LC1DT40G7?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1DT40G7 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1DT40G7
Material Number
—
Manufacturer
Schneider
Product ID
32797

Get a Free Quote

Request pricing and availability for LC1DT40G7.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current
40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
120 V AC 50/60 Hz
IP degree of protection
IP20 front face conforming to IEC 60529
See all specifications

Product Highlights

  1. 4-pole contactor with 4 NO power poles and 1 NO + 1 NC auxiliary contacts: TeSys Deca LC1D contactor rated 40 A at up to 440 V AC in AC-1, with a 120 V AC 50/60 Hz control coil
  2. Power circuit ratings: operational voltage up to 690 V AC (25...400 Hz) or 300 V DC, making capacity 450 A at 440 V, breaking capacity 450 A at 440 V, and power dissipation 3.2 W per pole in AC-1
  3. Durability: 15 million mechanical cycles and 1.4 million electrical cycles at 40 A AC-1 up to 440 V, with a maximum operating rate of 3600 cycles per hour at 60 °C
  4. Auxiliary contacts: mechanically linked 1 NO + 1 NC per IEC 60947-5-1 and mirror contact 1 NC per IEC 60947-4-1, with 1.5 ms non-overlap time on energisation and de-energisation
  5. Mounting and environment: rail or plate mounting, IP20 front face, ambient operating range -40...60 °C with derating up to 70 °C, and operating altitude up to 3000 m
LC1DT40G7

Product Information

Technical Specifications

Specifications for LC1DT40G7
ParameterValue
Product or component typeContactor
Range of productTeSys Deca Advanced
[Ue] rated operational voltagePower circuit: <= 690 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage120 V AC 50/60 Hz
Control circuit voltage limits0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
Power dissipation per pole3.2 W AC-1
RangeTeSys / TeSys Deca
Connections - terminalsControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 1 2.5…10 mm² - cable stiffness: flexible without cable endPower circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible without cable endPower circuit: screw clamp terminals 1 2.5…10 mm² - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 1 2.5…16 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 2 2.5…16 mm² - cable stiffness: solid without cable end
Height91 mm
Width45 mm
Depth99 mm
IP degree of protectionIP20 front face conforming to IEC 60529
Permissible ambient air temperature around the device-40…60 °C / 60…70 °C with derating
Product certificationsDNVGOSTBVGLCSAULLROS (Lloyds register of shipping)RINACCC