Industrial Automation Parts. Prompt replies from real people.

Schneider LC1D806M7 TeSys Deca Non-Reversing Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider LC1D806M7?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1D806M7 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1D806M7
Material Number
—
Manufacturer
Schneider
Product ID
32677

Get a Free Quote

Request pricing and availability for LC1D806M7.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 300 V DC 25...400 Hz / Power circuit: <= 1000 V AC
[Ie] rated operational current
125 A (at <60 °C) at <= 1000 V AC AC-1 for power circuit / 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit / 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage
220 V AC 50/60 Hz
IP degree of protection
IP20 front face conforming to IEC 60529
See all specifications

Product Highlights

  1. 3-pole contactor with 3 NO power poles and 1 NO + 1 NC auxiliary contacts: mechanically linked and mirror contact types per IEC 60947-5-1 and IEC 60947-4-1
  2. Rated operational current: 125 A AC-1 at up to 1000 V AC and 80 A AC-3/AC-3e at up to 440 V AC, at 60 °C
  3. Motor power ratings: 22 kW at 220-230 V AC, 37 kW at 380-400 V AC, 45 kW at 415-440 V AC, 55 kW at 500 V AC, and 45 kW at 660-690 V AC in AC-3 and AC-3e
  4. Control circuit: 220 V AC 50/60 Hz coil without built-in suppressor module, with 245 VA inrush and 26 VA hold-in power consumption
  5. Durability: 4 million mechanical cycles and 1.5 million electrical cycles at 80 A AC-3/AC-3e up to 440 V
  6. Mounting and connection: rail or plate mounting, power circuit bars or lugs-ring terminals up to 17 mm external diameter, control circuit lugs-ring terminals up to 8 mm external diameter
  7. Ambient operating temperature: -40 to 60 °C, with derating from 60 to 70 °C, and operating altitude up to 3000 m
LC1D806M7

Product Information

Technical Specifications

Specifications for LC1D806M7

ParameterValue
Product or component typeContactor
Range of productTeSys Deca Advanced
[Ue] rated operational voltagePower circuit: <= 300 V DC 25...400 Hz / Power circuit: <= 1000 V AC
[Ie] rated operational current125 A (at <60 °C) at <= 1000 V AC AC-1 for power circuit80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage220 V AC 50/60 Hz
Control circuit voltage limits0.85...1.1 Uc (-40…55 °C):operational AC 60 Hz0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz0.8...1.1 Uc (-40…55 °C):operational AC 50 Hz1...1.1 Uc (55…70 °C):operational AC 50/60 Hz
Motor power kW22 kW at 220/230 V AC 50/60 Hz (AC-3)37 kW at 380/400 V AC 50/60 Hz (AC-3)45 kW at 415/440 V AC 50/60 Hz (AC-3)55 kW at 500 V AC 50/60 Hz (AC-3)45 kW at 660/690 V AC 50/60 Hz (AC-3)45 kW at 1000 V AC 50/60 Hz (AC-3)22 kW at 220/230 V AC 50/60 Hz (AC-3e)37 kW at 380/400 V AC 50/60 Hz (AC-3e)45 kW at 415/440 V AC 50/60 Hz (AC-3e)55 kW at 500 V AC 50/60 Hz (AC-3e)45 kW at 660/690 V AC 50/60 Hz (AC-3e)45 kW at 1000 V AC 50/60 Hz (AC-3e)15 kW at 400 V AC 50/60 Hz (AC-4)
ParameterValue
RangeTeSys
Connections - terminalsControl circuit: lugs-ring terminals - external diameter: 8 mmPower circuit: bars 1 - busbar cross section: 3 x 16 mmPower circuit: lugs-ring terminals - external diameter: 17 mm
Height127 mm
Width85 mm
Depth130 mm
IP degree of protectionIP20 front face conforming to IEC 60529
Permissible ambient air temperature around the device-40…60 °C / 60…70 °C with derating
Product certificationsCCCULCB SchemeCSACEUKCAMarineEAC

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp