Product Model
LC1D65CW
Material Number
—
Manufacturer
Schneider
Product ID
32641

Get a Free Quote

Request pricing and availability for LC1D65CW.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current
65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit / 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
42 V AC 50 Hz
IP degree of protection
IP2X conforming to VDE 0106 / IP2X conforming to IEC 60529
See all specifications

Product Highlights

  1. Motor Power Ratings: 30 kW at 380...400 V AC 50 Hz, 37 kW at 500 V AC 50 Hz, 37 kW at 660...690 V AC 50 Hz, 18.5 kW at 220...230 V AC 50 Hz, 30 kW at 415 V AC 50 Hz, 37 kW at 1000 V AC 50 Hz, 30 kW at 440 V AC 50 Hz
  2. Maximum Horse Power Ratings: 5 hp at 115 V AC 60 Hz for 1 phase motors, 10 hp at 230/240 V AC 60 Hz for 1 phase motors, 20 hp at 200/208 V AC 60 Hz for 3 phase motors, 20 hp at 230/240 V AC 60 Hz for 3 phase motors, 40 hp at 460/480 V AC 60 Hz for 3 phase motors, 50 hp at 575/600 V AC 60 Hz for 3 phase motors
  3. Rated Operational Current: 65 A at <= 440 V AC AC-3 for power circuit, 80 A at <= 440 V AC AC-1 for power circuit, both at 140 °F (60 °C)
  4. Rated Operational Voltage: Power circuit <= 690 V AC, 25...400 Hz
  5. Control Circuit: 42 V AC 50 Hz, AC 50 Hz control circuit type, without built-in bidirectional peak limiting diode suppressor
  6. Utilisation Category: AC-1, AC-2, AC-3, AC-4
  7. Poles Description: 3P, 3 NO pole contact composition
  8. Auxiliary Contacts: 1 NO + 1 NC, with mirror contact 1 NC per IEC 60947-4-1 and mechanically linked 1 NO + 1 NC per IEC 60947-5-1
  9. Mechanical Durability: 6,000,000 cycles
  10. Safety Reliability Level: B10d = 20,000,000 cycles with mechanical load, B10d = 1,369,863 cycles with nominal load per EN/ISO 13849-1
  11. Standards and Certifications: IEC 60947-4-1, IEC 60947-5-1, UL 508, CSA C22.2 No 14, EN 60947-5-1, certified by GL, CSA, LROS, BV, CCC, UL, GOST, RINA
  12. Ambient Air Temperature: -40...140 °F (-40...60 °C) operation, 140...158 °F (60...70 °C) with derating, -76...176 °F (-60...80 °C) storage
  13. Operating Altitude: 0...9842.52 ft (0...3000 m)
  14. Dimensions and Weight: 5.00 in (127 mm) height, 3.0 in (75 mm) width, 4.7 in (119 mm) depth, 3.09 lb(US) (1.4 kg) net weight
LC1D65CW

Product Information

Technical Specifications

Specifications for LC1D65CW
ParameterValue
Product or component typeContactor
Range of productTeSys D
[Ue] rated operational voltagePower circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit / 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage42 V AC 50 Hz
Control circuit voltage limits0.75...1.25 Uc (-40…60 °C):operational DC1...1.25 Uc (60…70 °C):operational DC 50 Hz0.8...1.1 Uc (-40…55 °C):operational AC 50 Hz0.3...0.6 Uc (-40…70 °C):drop-out AC 50 Hz
Motor power kW30 kW at 380...400 V AC 50 Hz37 kW at 500 V AC 50 Hz37 kW at 660...690 V AC 50 Hz18.5 kW at 220...230 V AC 50 Hz30 kW at 415 V AC 50 Hz37 kW at 1000 V AC 50 Hz30 kW at 440 V AC 50 Hz
RangeTeSys
Connections - terminalsControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: rigid without cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable endPower circuit: screw terminals 1 2.5…25 mm² - cable stiffness: rigidPower circuit: screw terminals 2 2.5…16 mm² - cable stiffness: rigid without cable endPower circuit: screw terminals 1 2.5…25 mm² - cable stiffness: flexible without cable endPower circuit: screw terminals 2 2.5…16 mm² - cable stiffness: flexible without cable endPower circuit: screw terminals 1 2.5…25 mm² - cable stiffness: flexible with cable endPower circuit: screw terminals 2 2.5…10 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: rigidControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: rigid
Height127 mm
Width75 mm
Depth119 mm
IP degree of protectionIP2X conforming to VDE 0106 / IP2X conforming to IEC 60529
Permissible ambient air temperature around the device-60…80 °C storage-40…60 °C operation60…70 °C with derating
Product certificationsGLCSALROS (Lloyds register of shipping)BVCCCULGOSTRINABV