Industrial Automation Parts. Prompt replies from real people.

Schneider LC1D80G6 IEC Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider LC1D80G6?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1D80G6 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1D80G6
Material Number
—
Manufacturer
Schneider
Product ID
32601

Get a Free Quote

Request pricing and availability for LC1D80G6.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 300 V DC 25...400 Hz / Power circuit: <= 1000 V AC
[Ie] rated operational current
125 A (at <60 °C) at <= 1000 V AC AC-1 for power circuit / 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit / 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage
120 V AC 60 Hz
IP degree of protection
IP20 front face conforming to IEC 60529
See all specifications

Product Highlights

  1. Rated operational current: 80 A at up to 440 V AC in AC-3 and AC-3e, 125 A at up to 1000 V AC in AC-1, both at 60 °C
  2. Motor power: 22 kW at 220...230 V AC, 37 kW at 380...400 V AC, 45 kW at 415...440 V AC, 55 kW at 500 V AC, and 45 kW at 660...690 V AC in AC-3 and AC-3e
  3. Maximum horsepower rating: 60 hp at 460/480 V AC and 575/600 V AC for 3-phase motors, 30 hp at 200/208 V AC and 230/240 V AC for 3-phase motors, 15 hp at 230/240 V AC for 1-phase motors
  4. Coil and control: 120 V AC 60 Hz control circuit, 3 NO power poles, and 1 NO + 1 NC auxiliary contacts
  5. Durability: 10 million mechanical cycles and 1.5 million electrical cycles at 80 A AC-3/AC-3e up to 440 V
  6. Mounting and protection: rail or plate mounting, IP20 front face, and operating temperature range of -40...60 °C with derating up to 70 °C
LC1D80G6

Product Information

Technical Specifications

Specifications for LC1D80G6
ParameterValue
Product or component typeContactor
Range of productTeSys Deca Advanced
[Ue] rated operational voltagePower circuit: <= 300 V DC 25...400 Hz / Power circuit: <= 1000 V AC
[Ie] rated operational current125 A (at <60 °C) at <= 1000 V AC AC-1 for power circuit80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage120 V AC 60 Hz
Control circuit voltage limits0.85...1.1 Uc (-40…55 °C):operational AC 60 Hz0.3...0.6 Uc (-40…70 °C):drop-out AC 60 Hz1...1.1 Uc (55…70 °C):operational AC 60 Hz
Motor power kW22 kW at 220/230 V AC 50/60 Hz (AC-3)37 kW at 380/400 V AC 50/60 Hz (AC-3)45 kW at 415/440 V AC 50/60 Hz (AC-3)55 kW at 500 V AC 50/60 Hz (AC-3)45 kW at 660/690 V AC 50/60 Hz (AC-3)45 kW at 1000 V AC 50/60 Hz (AC-3)22 kW at 220/230 V AC 50/60 Hz (AC-3e)37 kW at 380/400 V AC 50/60 Hz (AC-3e)45 kW at 415/440 V AC 50/60 Hz (AC-3e)55 kW at 500 V AC 50/60 Hz (AC-3e)45 kW at 660/690 V AC 50/60 Hz (AC-3e)45 kW at 1000 V AC 50/60 Hz (AC-3e)15 kW at 400 V AC 50/60 Hz (AC-4)
RangeTeSys
Connections - terminalsControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable endPower circuit: connector 1 4…50 mm² - cable stiffness: flexible without cable endPower circuit: connector 2 4…25 mm² - cable stiffness: flexible without cable endPower circuit: connector 1 4…50 mm² - cable stiffness: flexible with cable endPower circuit: connector 2 4…16 mm² - cable stiffness: flexible with cable endPower circuit: connector 1 4…50 mm² - cable stiffness: solid without cable endPower circuit: connector 2 4…25 mm² - cable stiffness: solid without cable end
Height127 mm
Width85 mm
Depth130 mm
IP degree of protectionIP20 front face conforming to IEC 60529
Permissible ambient air temperature around the device-40…60 °C / 60…70 °C with derating
Product certificationsCCCULCB SchemeCSACEUKCAMarineEAC