LC1D80A6EHE
Material Number
—
Manufacturer
Schneider
Product ID
32567

Get a Free Quote

Request pricing and availability for LC1D80A6EHE.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
[Ie] rated operational current
80 A (at <140 °F (60 °C)) at <= 440 V AC-1 for power circuit / 66 A (at <140 °F (60 °C)) at <= 440 V AC-3 for power circuit / 66 A (at <140 °F (60 °C)) at <= 440 V AC-3e for power circuit
[Uc] control circuit voltage
48...130 V AC 50/60 Hz / 48...130 V DC
Maximum Horse Power Rating
5 hp at 115 V AC 60 Hz for 1 phase motors / 10 hp at 230/240 V AC 60 Hz for 1 phase motors / 20 hp at 200/208 V AC 60 Hz for 3 phase motors / 20 hp at 230/240 V AC 60 Hz for 3 phase motors / 40 hp at 460/480 V AC 60 Hz for 3 phase motors / 50 hp at 575/600 V AC 60 Hz for 3 phase motors
IP degree of protection
IP20 front face IEC 60529
See all specifications

Product Highlights

  1. Range: TeSys Deca contactor, device short name LC1D, 3-pole with 3 NO power poles
  2. Contactor application: Resistive load and motor control, utilisation categories AC-1, AC-3 and AC-3e
  3. Rated operational voltage: Power circuit up to 690 V AC, 25 to 400 Hz
  4. Rated operational current: 80 A at up to 440 V AC-1 and 66 A at up to 440 V AC-3 or AC-3e, both at 60 °C or lower
  5. Motor power: 18.5 kW at 220 to 230 V AC and 37 kW at 380 to 690 V AC, 50 Hz, AC-3
  6. Control circuit: 48 to 130 V AC 50/60 Hz or 48 to 130 V DC, AC/DC electronic coil with built-in bidirectional peak limiting
  7. Maximum horsepower rating: 5 hp at 115 V AC single-phase, 10 hp at 230/240 V AC single-phase, 20 hp at 200/208 V and 230/240 V AC three-phase, 40 hp at 460/480 V AC three-phase and 50 hp at 575/600 V AC three-phase, 60 Hz
  8. Auxiliary contacts: 1 NO + 1 NC, mechanically linked and mirror contact
  9. Durability: 6 million mechanical cycles and 1 million electrical cycles at 66 A AC-3 up to 440 V
  10. Mounting and protection: Plate or rail mounting, IP20 front face, operating altitude up to 3000 m
LC1D80A6EHE

Product Information

Technical Specifications

Specifications for LC1D80A6EHE

ParameterValue
Product or Component TypeContactor
Range of ProductTeSys Deca Advanced
[Ue] rated operational voltagePower circuit <= 690 V AC 25...400 Hz
[Ie] rated operational current80 A (at <140 °F (60 °C)) at <= 440 V AC-1 for power circuit66 A (at <140 °F (60 °C)) at <= 440 V AC-3 for power circuit66 A (at <140 °F (60 °C)) at <= 440 V AC-3e for power circuit
[Uc] control circuit voltage48...130 V AC 50/60 Hz / 48...130 V DC
Control circuit voltage limits<= 0.1 Uc (-40…158 °F (-40…70 °C)):drop-out AC/DC0.85...1.1 Uc (-40…140 °F (-40…60 °C)):operational AC/DC1...1.1 Uc (140…158 °F (60…70 °C)):operational AC/DC
Maximum Horse Power Rating5 hp at 115 V AC 60 Hz for 1 phase motors10 hp at 230/240 V AC 60 Hz for 1 phase motors20 hp at 200/208 V AC 60 Hz for 3 phase motors20 hp at 230/240 V AC 60 Hz for 3 phase motors40 hp at 460/480 V AC 60 Hz for 3 phase motors50 hp at 575/600 V AC 60 Hz for 3 phase motors
ParameterValue
Device short nameLC1D
Connections - terminalsPower circuit: lugs-ring terminals - external diameter: 0.6 in (16.5 mm) / Control circuit: lugs-ring terminals - external diameter: 0.3 in (8 mm)
Height4.8 in (122 mm)
Width2.2 in (55 mm)
Depth4.7 in (120 mm)
IP degree of protectionIP20 front face IEC 60529
Permissible ambient air temperature around the device-40…140 °F (-40…60 °C) / 140…158 °F (60…70 °C) with derating
Product CertificationsCCCCSAEACULKCDNV-GLLROS (Lloyds register of shipping)UKCA