Industrial Automation Parts. Prompt replies from real people.

Schneider LC1D65004P7 TeSys Deca Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider LC1D65004P7?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1D65004P7 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1D65004P7
Material Number
—
Manufacturer
Schneider
Product ID
32467

Get a Free Quote

Request pricing and availability for LC1D65004P7.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current
80 A (at <60 °C) AC AC-1 for power circuit
[Uc] control circuit voltage
230 V AC 50/60 Hz
IP degree of protection
IP2X conforming to IEC 60529 / IP2X conforming to VDE 0106
See all specifications

Product Highlights

  1. Contactor Type: TeSys Deca LC1D 4-pole contactor with 4 NO power poles and resistive-load (AC-1) application
  2. Utilisation Categories: AC-1, AC-3, AC-3e and AC-4
  3. Power Circuit Ratings: 80 A at up to 140 °F (60 °C) AC-1, up to 690 V AC at 25 to 400 Hz, 1000 A making and breaking capacity at 440 V per IEC 60947
  4. Control Circuit: 230 V AC 50/60 Hz coil with screw clamp terminals, 140/160 VA inrush and 13/15 VA hold-in power
  5. Motor Ratings: 5 hp at 115 V AC single phase, 10 hp at 230/240 V AC single phase, 20 hp at 200/208 V AC and 230/240 V AC three phase, 50 hp at 460/480 V AC and 575/600 V AC three phase, CSA and UL
  6. Durability and Environment: 6 million mechanical cycles, B10d 1369863 cycles at nominal load, operating temperature -5 to 60 °C, altitude up to 3000 m without derating
LC1D65004P7

Product Information

Technical Specifications

Specifications for LC1D65004P7
ParameterValue
Product or component typeContactor
Range of productTeSys Deca Advanced
[Ue] rated operational voltagePower circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current80 A (at <60 °C) AC AC-1 for power circuit
[Uc] control circuit voltage230 V AC 50/60 Hz
Control circuit voltage limits0.3...0.6 Uc (60 °C):drop-out AC 50/60 Hz0.8...1.1 Uc (60 °C):operational AC 50 Hz0.85...1.1 Uc (60 °C):operational AC 60 Hz
Motor power hp10 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to CSA10 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to UL20 hp at 200/208 V AC 60 Hz for 3 phases motors conforming to CSA20 hp at 200/208 V AC 60 Hz for 3 phases motors conforming to UL20 hp at 230/240 V AC 60 Hz for 3 phases motors conforming to CSA20 hp at 230/240 V AC 60 Hz for 3 phases motors conforming to UL5 hp at 115 V AC 60 Hz for 1 phase motors conforming to CSA5 hp at 115 V AC 60 Hz for 1 phase motors conforming to UL50 hp at 460/480 V AC 60 Hz for 3 phases motors conforming to CSA50 hp at 460/480 V AC 60 Hz for 3 phases motors conforming to UL50 hp at 575/600 V AC 60 Hz for 3 phases motors conforming to CSA50 hp at 575/600 V AC 60 Hz for 3 phases motors conforming to UL
Device short nameLC1D
Connections - terminalsControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 1 1…35 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 2 1…25 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 2 1…35 mm² - cable stiffness: solid without cable end
Height127 mm
Width85 mm
Depth130 mm
IP degree of protectionIP2X conforming to IEC 60529 / IP2X conforming to VDE 0106
Permissible ambient air temperature around the device-5…60 °C / -40…70 °C at Uc
Product certificationsCCCGOSTDNVULGLLROS (Lloyds register of shipping)BVRINACSAUKCA