Industrial Automation Parts. Prompt replies from real people.

Schneider LC1D50A6ND TeSys D Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider LC1D50A6ND?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1D50A6ND cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1D50A6ND
Material Number
—
Manufacturer
Schneider
Product ID
32363

Get a Free Quote

Request pricing and availability for LC1D50A6ND.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current
50 A (at <60 °C) at <= 440 V AC AC-3 for power circuit / 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
60 V DC
IP degree of protection
IP20 front face conforming to IEC 60529
See all specifications

Product Highlights

  1. Product Type: TeSys Deca contactor, device short name LC1D, 3-pole with 3 NO power poles
  2. Application: Motor control and resistive load, utilisation categories AC-1, AC-3 and AC-4
  3. Rated Operational Voltage: Power circuit up to 690 V AC at 25 to 400 Hz or up to 300 V DC
  4. Rated Operational Current: 50 A at up to 440 V AC (AC-3) and 80 A at up to 440 V AC (AC-1), both at up to 60 °C
  5. Motor Power Ratings: 15 kW at 220 to 230 V AC, 22 kW at 380 to 400 V AC, 25 kW at 415 V AC, 30 kW at 440 V AC, 30 kW at 500 V AC and 33 kW at 660 to 690 V AC at 50/60 Hz (AC-3), plus 11 kW at 400 V AC 50/60 Hz (AC-4)
  6. Maximum Horsepower Ratings: 3 hp at 115 V AC and 7.5 hp at 230/240 V AC for 1-phase motors, 15 hp at 200/208 V AC and 230/240 V AC for 3-phase motors, and 40 hp at 460/480 V AC and 575/600 V AC for 3-phase motors
  7. Control Circuit: 60 V DC standard DC control with built-in bidirectional peak limiting diode suppressor, 19 W inrush and 7.4 W hold-in power consumption at 20 °C
  8. Auxiliary Contacts: 1 NO + 1 NC, mechanically linked to IEC 60947-5-1 and mirror contact to IEC 60947-4-1
  9. Durability: 10 million mechanical cycles and 1.45 million electrical cycles at 50 A AC-3 up to 440 V or 0.5 million electrical cycles at 80 A AC-1 up to 440 V
  10. Protection and Standards: IP20 front face to IEC 60529, TH protective treatment, overvoltage category III, pollution degree 3, 6 kV rated impulse withstand voltage, conforming to IEC 60947-4-1, IEC 60947-5-1, UL 60947-4-1 and CSA C22.2 No 14
LC1D50A6ND

Product Information

Technical Specifications

Specifications for LC1D50A6ND

ParameterValue
Product or component typeContactor
Range of productTeSys Deca
[Ue] rated operational voltagePower circuit: <= 690 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current50 A (at <60 °C) at <= 440 V AC AC-3 for power circuit / 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage60 V DC
Control circuit voltage limits0.1...0.3 Uc (-40…70 °C):drop-out DC0.75...1.25 Uc (-40…60 °C):operational DC1...1.25 Uc (60…70 °C):operational DC
Motor power kW15 kW at 220...230 V AC 50/60 Hz (AC-3)22 kW at 380...400 V AC 50/60 Hz (AC-3)30 kW at 500 V AC 50/60 Hz (AC-3)33 kW at 660...690 V AC 50/60 Hz (AC-3)25 kW at 415 V AC 50/60 Hz (AC-3)30 kW at 440 V AC 50/60 Hz (AC-3)11 kW at 400 V AC 50/60 Hz (AC-4)
ParameterValue
RangeTeSys / TeSys Deca
Connections - terminalsControl circuit: lugs-ring terminals - external diameter: 8 mm / Power circuit: lugs-ring terminals - external diameter: 16.5 mm
Height122 mm
Width55 mm
Depth120 mm
IP degree of protectionIP20 front face conforming to IEC 60529
Permissible ambient air temperature around the device-40…60 °C / 60…70 °C with derating
Product certificationsCCCULCB SchemeCSACEUKCAMarineEAC

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.