Industrial Automation Parts. Prompt replies from real people.

Schneider LC1D656P7 TeSys Deca Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider LC1D656P7?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1D656P7 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1D656P7
Material Number
—
Manufacturer
Schneider
Product ID
32319

Get a Free Quote

Request pricing and availability for LC1D656P7.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current
80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit / 65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
[Uc] control circuit voltage
380 V AC 50/60 Hz
IP degree of protection
IP2X conforming to IEC 60529 / IP2X conforming to VDE 0106
See all specifications

Product Highlights

  1. Range and device: TeSys Deca contactor, device short name LC1D, 3-pole with 3 NO power poles
  2. Contactor application: Motor control and resistive load, utilisation categories AC-1, AC-2, AC-3 and AC-4
  3. Rated operational voltage: Power circuit up to 690 V AC, 25 to 400 Hz
  4. Rated operational current: 80 A at up to 440 V AC in AC-1 and 65 A at up to 440 V AC in AC-3, both at 60 °C
  5. Motor power: 18.5 kW at 220 to 230 V AC, 30 kW at 380 to 400 V AC, 30 kW at 415 V AC, 30 kW at 440 V AC, 37 kW at 500 V AC, 37 kW at 660 to 690 V AC and 37 kW at 1000 V AC, all at 50 Hz
  6. Maximum horse power rating: 5 hp at 115 V AC and 10 hp at 230/240 V AC for 1-phase motors, 20 hp at 200/208 V AC, 20 hp at 230/240 V AC, 40 hp at 460/480 V AC and 50 hp at 575/600 V AC for 3-phase motors, all at 60 Hz
  7. Control circuit: 380 V AC coil at 50/60 Hz, AC control circuit type, without built-in bidirectional peak limiting diode suppressor
  8. Auxiliary contacts: 1 NO + 1 NC, mechanically linked and mirror contact
  9. Durability: 6,000,000 mechanical cycles and B10d of 1,369,863 cycles with nominal load or 20,000,000 cycles with mechanical load per EN/ISO 13849-1
  10. Protection and environment: IP2X degree of protection, 8 kV rated impulse withstand voltage, overvoltage category III, operating temperature -40 to 60 °C with derating to 70 °C, storage -60 to 80 °C, operating altitude up to 3000 m
  11. Standards and certifications: IEC 60947-4-1, IEC 60947-5-1, UL 508, EN 60947-4-1 and EN 60947-5-1, with UL, CSA, CCC, GL, DNV, RINA and LROS certifications
LC1D656P7

Product Information

Technical Specifications

Specifications for LC1D656P7

ParameterValue
Product or component typeContactor
Range of productTeSys Deca
[Ue] rated operational voltagePower circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit / 65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
[Uc] control circuit voltage380 V AC 50/60 Hz
Control circuit voltage limits0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz1...1.1 Uc (60…70 °C):operational AC 50/60 Hz0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
Motor power kW37 kW at 500 V AC 50 Hz37 kW at 660...690 V AC 50 Hz18.5 kW at 220...230 V AC 50 Hz30 kW at 415 V AC 50 Hz37 kW at 1000 V AC 50 Hz30 kW at 440 V AC 50 Hz30 kW at 380...400 V AC 50 Hz
ParameterValue
RangeTeSys
Connections - terminalsControl circuit: lugs - external diameter: 8 mm / Power circuit: lugs - external diameter: 16 mm
Height127 mm
Width75 mm
Depth119 mm
IP degree of protectionIP2X conforming to IEC 60529 / IP2X conforming to VDE 0106
Permissible ambient air temperature around the device-60…80 °C storage-40…60 °C operation60…70 °C with derating
Product certificationsRINAGLLROS (Lloyds register of shipping)ULDNVCSACCCCSAGL

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp