Schneider LC1D38CD Electric 38 AMP Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider LC1D38CD?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1D38CD cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1D38CD
Material Number
—
Manufacturer
Schneider
Product ID
32099

Get a Free Quote

Request pricing and availability for LC1D38CD.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current
50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit / 38 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
[Uc] control circuit voltage
36 V DC
IP degree of protection
IP20 front face conforming to IEC 60529
See all specifications

Product Highlights

  1. Motor and Load Ratings: 3-pole contactor rated 38 A AC-3 and 50 A AC-1 at up to 440 V AC, with motor power ratings from 9 kW at 220...230 V AC to 18.5 kW at 660...690 V AC in AC-3 and 7.5 kW at 400 V AC in AC-4
  2. Horsepower Ratings: 10 hp at 200/208 V and 230/240 V AC, 20 hp at 480 V AC, and 25 hp at 600 V AC for 3-phase motors, plus 5 hp at 240 V AC for 1-phase motors
  3. Control Circuit: 36 V DC control circuit with built-in bidirectional peak limiting diode suppressor, 5.4 W inrush and hold-in power, and 20 ms opening and 63 ms closing times
  4. Auxiliary Contacts: 1 NO + 1 NC auxiliary contacts, mechanically linked per IEC 60947-5-1 and mirror contact per IEC 60947-4-1
  5. Durability: 30 million mechanical cycles and 1.4 million electrical cycles at 50 A AC-1 or 38 A AC-3 up to 440 V
  6. Terminations and Mounting: Screw clamp terminals for control and power circuits with 1.7 N.m and 2.5 N.m tightening torque, mounted on plate or rail
  7. Standards and Protection: Compliant with IEC 60947-4-1, IEC 60947-5-1, EN 60947-4-1, EN 60947-5-1, UL 508, and CSA C22.2 No 14, with IP20 front face protection
LC1D38CD

Product Information

Technical Specifications

Specifications for LC1D38CD
ParameterValue
Product or component typeContactor
Range of productTeSys Deca
[Ue] rated operational voltagePower circuit: <= 690 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit / 38 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
[Uc] control circuit voltage36 V DC
Control circuit voltage limits0.1...0.25 Uc (-40…70 °C):drop-out DC0.7...1.25 Uc (-40…60 °C):operational DC1...1.25 Uc (60…70 °C):operational DC
Motor power kW18.5 kW at 500 V AC 50/60 Hz (AC-3)18.5 kW at 660...690 V AC 50/60 Hz (AC-3)7.5 kW at 400 V AC 50/60 Hz (AC-4)18.5 kW at 380...400 V AC 50/60 Hz (AC-3)9 kW at 220...230 V AC 50/60 Hz (AC-3)18.5 kW at 415...440 V AC 50/60 Hz (AC-3)
RangeTeSys
Connections - terminalsControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 1 2.5…10 mm² - cable stiffness: flexible without cable endPower circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible without cable endPower circuit: screw clamp terminals 1 1…10 mm² - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 2 1.5…6 mm² - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 1 1.5…10 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: solid without cable end
Height85 mm
Width45 mm
Depth101 mm
IP degree of protectionIP20 front face conforming to IEC 60529
Permissible ambient air temperature around the device-40…60 °C / 60…70 °C with derating
Product certificationsCSADNVLROS (Lloyds register of shipping)RINAULGOSTBVGLCCC

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.