Industrial Automation Parts. Prompt replies from real people.

Schneider LC1D40A3B7 TeSys Deca Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider LC1D40A3B7?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1D40A3B7 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1D40A3B7
Material Number
—
Manufacturer
Schneider
Product ID
31976

Get a Free Quote

Request pricing and availability for LC1D40A3B7.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current
60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit / 40 A (at <60 °C) at <= 440 V AC AC-3 for power circuit / 40 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage
24 V AC 50/60 Hz
IP degree of protection
IP20 front face conforming to IEC 60529
See all specifications

Product Highlights

  1. Current Ratings: 60 A AC-1 and 40 A AC-3/AC-3e at up to 440 V AC and 60 °C
  2. Motor Power Ratings: 18.5 kW at 380...400 V AC, 11 kW at 220...230 V AC, 22 kW at 415...440 V AC, 22 kW at 500 V AC, and 30 kW at 660...690 V AC in AC-3 and AC-3e, plus 9 kW at 400 V AC in AC-4
  3. Utilisation Categories: AC-1, AC-3, AC-3e, and AC-4
  4. Rated Operational Voltage: Power circuit up to 690 V AC at 25...400 Hz or up to 300 V DC
  5. Control Circuit: 24 V AC at 50/60 Hz with spring terminals
  6. Poles and Contacts: 3 NO power poles plus 1 NO + 1 NC auxiliary contacts
  7. Mounting: Plate or DIN rail
LC1D40A3B7

Product Information

Technical Specifications

Specifications for LC1D40A3B7

ParameterValue
Product or component typeContactor
Range of productTeSys Deca Advanced
[Ue] rated operational voltagePower circuit: <= 690 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit40 A (at <60 °C) at <= 440 V AC AC-3 for power circuit40 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage24 V AC 50/60 Hz
Control circuit voltage limits0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
Motor power kW11 kW at 220/230 V AC 50/60 Hz (AC-3)18.5 kW at 380/400 V AC 50/60 Hz (AC-3)22 kW at 415/440 V AC 50/60 Hz (AC-3)22 kW at 500 V AC 50/60 Hz (AC-3)30 kW at 660/690 V AC 50/60 Hz (AC-3)11 kW at 220/230 V AC 50/60 Hz (AC-3e)18.5 kW at 380/400 V AC 50/60 Hz (AC-3e)22 kW at 415/440 V AC 50/60 Hz (AC-3e)22 kW at 500 V AC 50/60 Hz (AC-3e)30 kW at 660/690 V AC 50/60 Hz (AC-3e)9 kW at 400 V AC 50/60 Hz (AC-4)
RangeTeSys / TeSys Deca
ParameterValue
Connections - terminalsControl circuit: spring terminals 1 0.75…2.5 mm² - cable stiffness: flexible without cable endControl circuit: spring terminals 2 0.75…2.5 mm² - cable stiffness: flexible without cable endPower circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: flexible without cable endPower circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: flexible without cable endPower circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: flexible with cable endPower circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: flexible with cable endPower circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: solid without cable endPower circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: solid without cable end
Height122 mm
Width55 mm
Depth120 mm
IP degree of protectionIP20 front face conforming to IEC 60529
Permissible ambient air temperature around the device-40…60 °C / 60…70 °C with derating
Product certificationsCCCULCB SchemeCSACEUKCAMarineEAC

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp