Industrial Automation Parts. Prompt replies from real people.

Schneider LC1D40A6BD IEC Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider LC1D40A6BD?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1D40A6BD cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1D40A6BD
Material Number
—
Manufacturer
Schneider
Product ID
31855

Get a Free Quote

Request pricing and availability for LC1D40A6BD.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current
60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit / 40 A (at <60 °C) at <= 440 V AC AC-3 for power circuit / 40 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage
24 V DC
IP degree of protection
IP20 front face conforming to IEC 60529
See all specifications

Product Highlights

  1. Motor control ratings: 40 A AC-3/AC-3e and 60 A AC-1 at up to 440 V AC, with 18.5 kW at 380...400 V AC and 30 kW at 660...690 V AC in AC-3
  2. Horsepower ratings: 30 hp at 460/480 V AC and 575/600 V AC for 3-phase motors, 10 hp at 200/208 V AC and 230/240 V AC for 3-phase motors
  3. Control circuit: 24 V DC coil with built-in bidirectional peak limiting diode suppressor, 19 W inrush and 7.4 W hold-in power
  4. Contact configuration: 3-pole, 3 NO power poles plus mechanically linked and mirror-contact auxiliary contacts (1 NO + 1 NC)
  5. Durability: 10 million mechanical cycles and 1.5 million electrical cycles at 40 A AC-3/AC-3e up to 440 V
LC1D40A6BD

Product Information

Technical Specifications

Specifications for LC1D40A6BD

ParameterValue
Product or component typeContactor
Range of productTeSys Deca Advanced
[Ue] rated operational voltagePower circuit: <= 690 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit40 A (at <60 °C) at <= 440 V AC AC-3 for power circuit40 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage24 V DC
Control circuit voltage limits0.1...0.3 Uc (-40…70 °C):drop-out DC0.75...1.25 Uc (-40…60 °C):operational DC1...1.25 Uc (60…70 °C):operational DC
Motor power kW11 kW at 220/230 V AC 50/60 Hz (AC-3)18.5 kW at 380/400 V AC 50/60 Hz (AC-3)22 kW at 415/440 V AC 50/60 Hz (AC-3)22 kW at 500 V AC 50/60 Hz (AC-3)30 kW at 660/690 V AC 50/60 Hz (AC-3)11 kW at 220/230 V AC 50/60 Hz (AC-3e)18.5 kW at 380/400 V AC 50/60 Hz (AC-3e)22 kW at 415/440 V AC 50/60 Hz (AC-3e)22 kW at 500 V AC 50/60 Hz (AC-3e)30 kW at 660/690 V AC 50/60 Hz (AC-3e)9 kW at 400 V AC 50/60 Hz (AC-4)
ParameterValue
RangeTeSys / TeSys Deca
Connections - terminalsControl circuit: lugs-ring terminals - external diameter: 8 mm / Power circuit: lugs-ring terminals - external diameter: 16.5 mm
Height122 mm
Width55 mm
Depth120 mm
IP degree of protectionIP20 front face conforming to IEC 60529
Permissible ambient air temperature around the device-40…60 °C / 60…70 °C with derating
Product certificationsCCCULCB SchemeCSACEUKCAMarineEAC

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp