| Product or component type | Contactor |
|---|
| Range of product | TeSys Deca Advanced |
|---|
| [Ue] rated operational voltage | Power circuit: <= 690 V AC 25...400 Hz |
|---|
| [Ie] rated operational current | 32 A (at <60 °C) at <= 440 V AC-3 for power circuit50 A (at <60 °C) at <= 440 V AC-1 for power circuit32 A (at <60 °C) at <= 440 V AC-3e for power circuit |
|---|
| [Uc] control circuit voltage | 48...130 V AC 50/60 Hz / 48...130 V DC |
|---|
| Control circuit voltage limits | <= 0.1 Uc (-40…70 °C):drop-out AC/DC0.85...1.1 Uc (-40…60 °C):operational AC/DC1...1.1 Uc (60…70 °C):operational AC/DC |
|---|
| Motor power kW | 7.5 kW at 220/230 V AC 50/60 Hz (AC-3)15 kW at 380/400 V AC 50/60 Hz (AC-3)15 kW at 415 V AC 50/60 Hz (AC-3)15 kW at 440 V AC 50/60 Hz (AC-3)18.5 kW at 500 V AC 50/60 Hz (AC-3)18.5 kW at 660/690 V AC 50/60 Hz (AC-3)7.5 kW at 220/230 V AC 50/60 Hz (AC-3e)15 kW at 380/400 V AC 50/60 Hz (AC-3e)15 kW at 415 V AC 50/60 Hz (AC-3e)15 kW at 440 V AC 50/60 Hz (AC-3e)18.5 kW at 500 V AC 50/60 Hz (AC-3e)18.5 kW at 660/690 V AC 50/60 Hz (AC-3e) |
|---|
| Device short name | LC1D |
|---|
| Connections - terminals | Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solidControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solidPower circuit: screw clamp terminals 1 2.5…10 mm² - cable stiffness: flexible without cable endPower circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible without cable endPower circuit: screw clamp terminals 1 1…10 mm² - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 2 1.5…6 mm² - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 1 1.5…10 mm² - cable stiffness: solidPower circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: solid |
|---|
| Height | 85 mm |
|---|
| Width | 45 mm |
|---|
| Depth | 92 mm |
|---|
| IP degree of protection | IP20 front face conforming to IEC 60529 |
|---|
| Permissible ambient air temperature around the device | -40…60 °C / 60…70 °C with derating |
|---|
| Product certifications | CCCCSAEACULKCDNV-GLLROS (Lloyds register of shipping)UKCA |
|---|