Industrial Automation Parts. Prompt replies from real people.

Schneider ATS48D62Y Soft Starter

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/24/2026

Q1Can you supply the Schneider ATS48D62Y?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider ATS48D62Y cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
ATS48D62Y
Material Number
—
Manufacturer
Schneider
Product ID
31756

Get a Free Quote

Request pricing and availability for ATS48D62Y.

More parts to source? Send your whole list in one enquiry

Key specifications

Product or component type
Soft starter
Range of product
Altistart 48
Ue power supply voltage
208...690 V - 15...10 %
power supply frequency
50...60 Hz - 5...5 %
Motor power kW
11 kW at 230 V for severe applications / 15 kW at 230 V for standard applications / 22 kW at 400 V for severe applications / 22 kW at 440 V for severe applications / 30 kW at 400 V for standard applications / 30 kW at 440 V for standard applications / 30 kW at 500 V for severe applications / 30 kW at 525 V for severe applications / 37 kW at 500 V for standard applications / 37 kW at 525 V for standard applications / 37 kW at 660 V for severe applications / 37 kW at 690 V for severe applications / 45 kW at 660 V for standard applications / 45 kW at 690 V for standard applications
Communication port protocol
Modbus
See all specifications

Product Highlights

  1. Product Type: Altistart 48 soft starter, short name ATS48, for asynchronous motors in heavy duty industry and pumps
  2. Supply: 208...690 V three-phase input at 50...60 Hz, with -15...10 % voltage tolerance and -5...5 % frequency tolerance
  3. Motor Power Ratings: 11 kW at 230 V severe, 15 kW at 230 V standard, 22 kW at 400/440 V severe, 30 kW at 400/440 V standard, 30 kW at 500/525 V severe, 37 kW at 500/525 V standard, 37 kW at 660/690 V severe, 45 kW at 660/690 V standard
  4. Horse Power Ratings: 15 hp at 208 V standard, 15 hp at 230 V severe, 20 hp at 230 V standard, 30 hp at 460 V severe, 40 hp at 460 V standard, 40 hp at 575 V severe, 50 hp at 575 V standard
  5. Protection: Phase failure, motor thermal protection and starter thermal protection
  6. Control and Communication: 5 discrete inputs, 2 discrete outputs, 3 relay outputs, 0-20 mA or 4-20 mA analogue output, Modbus RS485 multidrop serial link via RJ45
  7. Compliance: EN/IEC 60947-4-2, utilisation category AC-53A, CE marking, certifications NOM 117, GOST, TCF, UL, DNV, CCC, SEPRO, C-tick, CSA
  8. Operating Conditions: -10...40 °C without derating, 40...60 °C with 2 % per °C current derating, up to 1000 m without derating, 1000...2000 m with 2.2 % per 100 m current derating, 0...95 % relative humidity without condensation
ATS48D62Y

Product Information

Technical Specifications

Specifications for ATS48D62Y

ParameterValue
Product or component typeSoft starter
Range of productAltistart 48
Ue power supply voltage208...690 V - 15...10 %
power supply frequency50...60 Hz - 5...5 %
Motor power kW11 kW at 230 V for severe applications15 kW at 230 V for standard applications22 kW at 400 V for severe applications22 kW at 440 V for severe applications30 kW at 400 V for standard applications30 kW at 440 V for standard applications30 kW at 500 V for severe applications30 kW at 525 V for severe applications37 kW at 500 V for standard applications37 kW at 525 V for standard applications37 kW at 660 V for severe applications37 kW at 690 V for severe applications45 kW at 660 V for standard applications45 kW at 690 V for standard applications
Motor power hp15 hp at 208 V for standard applications15 hp at 230 V for severe applications20 hp at 230 V for standard applications30 hp at 460 V for severe applications40 hp at 460 V for standard applications40 hp at 575 V for severe applications50 hp at 575 V for standard applications
ParameterValue
Minimum switching current10 mA at 6 V DC for relay outputs
Communication port protocolModbus
Device connectionIn the motor supply line
Height290 mm
Width190 mm
Depth235 mm
Ambient air temperature for operation40…60 °C (with current derating of 2 % per °C) / -10…40 °C (without derating)
Ambient air temperature for storage-25…70 °C
Product certificationsNOM 117GOSTTCFULDNVCCCSEPROC-TickCSA

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp