Industrial Automation Parts. Prompt replies from real people.

Schneider LC1D258F7 TeSys Deca Non-Reversing Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider LC1D258F7?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1D258F7 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1D258F7
Material Number
—
Manufacturer
Schneider
Product ID
31677

Get a Free Quote

Request pricing and availability for LC1D258F7.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current
40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
110 V AC 50/60 Hz
IP degree of protection
IP20 front face conforming to IEC 60529
See all specifications

Product Highlights

  1. Contactor Application: Resistive load (AC-1), with utilisation categories AC-1, AC-3, AC-3e and AC-4
  2. Rated Operational Current: 40 A at up to 440 V AC, AC-1, at 60 °C for power circuit
  3. Control Circuit: 110 V AC 50/60 Hz, screw clamp terminals, without built-in suppressor module
  4. Poles Description: 4P with 2 NO + 2 NC pole contact composition and 1 NO + 1 NC mechanically linked auxiliary contacts
  5. Rated Operational Voltage: Power circuit up to 690 V AC, 25 to 400 Hz
  6. Conventional Free Air Thermal Current: 40 A at 60 °C for power circuit, 10 A at 60 °C for signalling circuit
  7. Rated Making and Breaking Capacity: 450 A at 440 V for power circuit per IEC 60947
  8. Rated Short-time Withstand Current: 240 A at 40 °C for 10 s for power circuit
  9. Compliance: IEC 60335-1 Clause 30.2 and IEC 60335-2-40 Annex JJ, with 850 °C fire resistance per IEC 60695-2-1
  10. Protective Cover: With
LC1D258F7

Product Information

Technical Specifications

Specifications for LC1D258F7
ParameterValue
Product or component typeContactor
Range of productTeSys Deca Advanced
[Ue] rated operational voltagePower circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage110 V AC 50/60 Hz
Control circuit voltage limits0.3...0.6 Uc (-40…60 °C):drop-out AC 50/60 Hz0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
Power dissipation per pole3.2 W AC-1
Device short nameLC1D
Connections - terminalsControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 1 2.5…10 mm² - cable stiffness: flexible without cable endPower circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible without cable endPower circuit: screw clamp terminals 1 2.5…10 mm² - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 1 2.5…16 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 2 2.5…16 mm² - cable stiffness: solid without cable end
Height91 mm
Width45 mm
Depth99 mm
IP degree of protectionIP20 front face conforming to IEC 60529
Permissible ambient air temperature around the device-40…60 °C / 60…70 °C with derating
Product certificationsULCCCCSAMarineUKCAEACCB Scheme

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.