Industrial Automation Parts. Prompt replies from real people.

Schneider LC1D186P7 TeSys Deca Nonreversing Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider LC1D186P7?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1D186P7 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1D186P7
Material Number
—
Manufacturer
Schneider
Product ID
31640

Get a Free Quote

Request pricing and availability for LC1D186P7.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current
18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit / 32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit / 18 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage
230 V AC 50/60 Hz
IP degree of protection
IP20 front face conforming to IEC 60529
See all specifications

Product Highlights

  1. Product Type: TeSys Deca contactor, device short name LC1D
  2. Contactor Application: Motor control and resistive load
  3. Utilisation Category: AC-1, AC-3, AC-3e, AC-4
  4. Poles Description: 3P with 3 NO pole contact composition and 1 NO + 1 NC auxiliary contacts
  5. Rated Operational Voltage: Power circuit up to 690 V AC at 25 to 400 Hz and up to 300 V DC
  6. Rated Operational Current: 18 A at up to 440 V AC in AC-3 and AC-3e, 32 A at up to 440 V AC in AC-1, all at up to 60 °C
  7. Control Circuit Voltage: 230 V AC at 50/60 Hz
  8. Motor Power: 4 kW at 220 to 230 V AC, 7.5 kW at 380 to 400 V AC, 9 kW at 415 to 440 V AC, 10 kW at 500 V AC, and 10 kW at 660 to 690 V AC, all at 50/60 Hz in AC-3 and AC-3e
  9. Motor Power: 4 kW at 400 V AC at 50/60 Hz in AC-4
  10. Terminals: Lugs-ring terminals
LC1D186P7

Product Information

Technical Specifications

Specifications for LC1D186P7

ParameterValue
Product or component typeContactor
Range of productTeSys Deca Advanced
[Ue] rated operational voltagePower circuit: <= 690 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit18 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage230 V AC 50/60 Hz
Control circuit voltage limits0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
Motor power kW4 kW at 220/230 V AC 50/60 Hz (AC-3)7.5 kW at 380/400 V AC 50/60 Hz (AC-3)9 kW at 415/440 V AC 50/60 Hz (AC-3)10 kW at 500 V AC 50/60 Hz (AC-3)10 kW at 660/690 V AC 50/60 Hz (AC-3)4 kW at 220/230 V AC 50/60 Hz (AC-3e)7.5 kW at 380/400 V AC 50/60 Hz (AC-3e)9 kW at 415/440 V AC 50/60 Hz (AC-3e)10 kW at 500 V AC 50/60 Hz (AC-3e)10 kW at 660/690 V AC 50/60 Hz (AC-3e)4 kW at 400 V AC 50/60 Hz (AC-4)
ParameterValue
Device short nameLC1D
Connections - terminalsControl circuit: lugs-ring terminals - external diameter: 8 mm / Power circuit: lugs-ring terminals - external diameter: 8 mm
Height77 mm
Width45 mm
Depth86 mm
IP degree of protectionIP20 front face conforming to IEC 60529
Permissible ambient air temperature around the device-40…60 °C / 60…70 °C with derating
Product certificationsULCCCCSAMarineUKCAEACCB Scheme

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp