Industrial Automation Parts. Prompt replies from real people.

Schneider LC1D115UD Contactors and Protection Relays

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider LC1D115UD?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1D115UD cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1D115UD
Material Number
—
Manufacturer
Schneider
Product ID
31335

Get a Free Quote

Request pricing and availability for LC1D115UD.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 1000 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current
200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit / 115 A (at <60 °C) at <= 440 V AC AC-3 for power circuit / 115 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage
250 V DC
IP degree of protection
IP20 front face conforming to IEC 60529
See all specifications

Product Highlights

  1. Contactor Type: TeSys Deca 3-pole contactor with 3 NO power poles and a protective cover
  2. Power Ratings: AC-3 motor ratings from 30 kW at 220...230 V AC to 65 kW at 1000 V AC, with 18.5 kW at 400 V AC in AC-4
  3. Current Ratings: 200 A AC-1 and 115 A AC-3/AC-3e at up to 440 V AC and 60 °C, 200 A conventional free air thermal current
  4. Control Circuit: 250 V DC control with integral suppression device, 270...365 W inrush and 2.4...5.1 W hold-in power
  5. Auxiliary Contacts: 1 NO + 1 NC mechanically linked and mirror contacts
  6. Durability: 8 million mechanical cycles and up to 0.95 million electrical cycles at 115 A AC-3/AC-3e
  7. Terminations: Screw clamp control terminals and connector power terminals accepting 10...120 mm² conductors
  8. Standards and Protection: IEC 60947-4-1, IEC 60947-5-1, UL 508 and CSA C22.2 No 14, IP20 front face, 8 kV impulse withstand
LC1D115UD

Product Information

Technical Specifications

Specifications for LC1D115UD

ParameterValue
Product or component typeContactor
Range of productTeSys Deca
[Ue] rated operational voltagePower circuit: <= 1000 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit115 A (at <60 °C) at <= 440 V AC AC-3 for power circuit115 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage250 V DC
Control circuit voltage limits0.75...1.2 Uc (-40…55 °C):operational DC0.15...0.4 Uc (-40…70 °C):drop-out DC1...1.2 Uc (55…70 °C):operational DC
Motor power kW30 kW at 220...230 V AC 50/60 Hz (AC-3)55 kW at 380...400 V AC 50/60 Hz (AC-3)59 kW at 415...440 V AC 50/60 Hz (AC-3)75 kW at 500 V AC 50/60 Hz (AC-3)80 kW at 660...690 V AC 50/60 Hz (AC-3)65 kW at 1000 V AC 50/60 Hz (AC-3)18.5 kW at 400 V AC 50/60 Hz (AC-4)30 kW at 220...230 V AC 50/60 Hz (AC-3e)55 kW at 380...400 V AC 50/60 Hz (AC-3e)59 kW at 415...440 V AC 50/60 Hz (AC-3e)75 kW at 500 V AC 50/60 Hz (AC-3e)80 kW at 660...690 V AC 50/60 Hz (AC-3e)65 kW at 1000 V AC 50/60 Hz (AC-3e)
RangeTeSys
ParameterValue
Connections - terminalsControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: solid without cable endControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: solid without cable endPower circuit: connector 1 10…120 mm² - cable stiffness: flexible without cable endPower circuit: connector 2 10…50 mm² - cable stiffness: flexible without cable endPower circuit: connector 1 10…120 mm² - cable stiffness: flexible with cable endPower circuit: connector 2 10…50 mm² - cable stiffness: flexible with cable endPower circuit: connector 1 10…120 mm² - cable stiffness: solid without cable endPower circuit: connector 2 10…50 mm² - cable stiffness: solid without cable end
Height158 mm
Width120 mm
Depth136 mm
IP degree of protectionIP20 front face conforming to IEC 60529
Permissible ambient air temperature around the device-40…60 °C / 60…70 °C with derating
Product certificationsCSABVGLCCCULDNVRINALROS (Lloyds register of shipping)GOSTUKCACE

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp